Notifier Onyx 640 to BACnet IP QuickServer Gateway

A FieldServer QuickServer Gateway that converts data between Notifier Onyx 640 and BACnet IP.
Our QuickServers are high performance, fully configurable, cost effective Building and Industrial Automation gateways to easily interface devices to networks in commercial buildings and industrial plants.
Every QuickServer includes browser-based tools for quick set-up and to perform diagnostics including determination of status, network settings, node information, map descriptors and more.
The premium QuickServer FS-QS-3X10 series comes equipped with dual Ethernet ports, RS485 and RS232 serial ports and is available with up to 10k point capacity.
The BACnet/IP driver allows the FieldServer to transfer data to and from devices over Ethernet using BACnet/IP protocol.
The NFS-640 Serial driver allows the FieldServer to record data from Notifier Onyx Series NFS-640, NFS2-640 and NFS-320 Fire Panels over RS-232.
SKU:
FS-QS-3020-0342 (250 points),FS-QS-3120-0342 (500 points),FS-QS-3220-0342 (1000 points),FS-QS-3320-0342 (3000 points),FS-QS-3420-0342 (5000 points),FS-QS-3520-0342 (10000 points);
FS-QS-2020-0342 (250 points),FS-QS-2120-0342 (1000 points),FS-QS-2220-0342 (500 points),FS-QS-2320-0342 (3000 points),FS-QS-2420-0342 (5000 points);
FS-QS-1020-0342 (250 points),FS-QS-1220-0342 (500 points),FS-QS-1320-0342 (3000 points),FS-QS-1420-0342 (5000 points);
QS-2xx0 QuickServer - QS-2xx0 - Single Ethernet Gateway Picture

A FieldServer QuickServer Gateway that converts data between Notifier Onyx 640 and BACnet IP.

BACnet IP

The BACnet/IP driver allows the FieldServer to transfer data to and from devices over Ethernet using BACnet/IP protocol. The FieldServer can emulate either a Server or Client.

All information in a BACnet system is represented in terms of objects. The Object_Identifier is a 32-bit code that identifies the type of Object (also identified by the Object_Type Property) and its "Instance" number, which together uniquely identify the Object within its BACnet device. Theoretically, a BACnet device could have over four million Objects of a particular type. The Object_Name is a text string, which has a unique capability.

BACnet devices may broadcast queries for devices that contain Objects with a specific Object_Name. This can greatly simplify project setup.

BACnet requires one Device Object to be present in every BACnet device. The Device Object makes information about the device and its capabilities available to other devices on the networks. Before one BACnet device starts control-related communications with another, it needs to obtain some of the information presented by the other device's Device Object. Unlike other Objects, the Device Object's Instance number must be unique across the entire BACnet internetwork because it is used to uniquely identify the BACnet devices. It may be used to conveniently identify the BACnet device from other devices during installation.

Standard object types are used to hold real time data and other information. Each Object Type is referenced by a number, for example 0 represents an Analog Input. See Appendix D.1 for abbreviation list.

Each Object consists of a number of prescribed properties, the main property being the Present_Value. Objects are monitored and controlled through their properties.

The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

Classic QuickServer Gateway (Serial-Ethernet)

QuickServer is a high performance, fully configurable, cost-effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators worldwide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost-effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

QuickServer (Serial-Ethernet) is available in two series:

The FS-QS-1X10 Series is preloaded with two BAS drivers (two RS485 serial ports and one Ethernet port) Drivers from a list of over 150 protocols. There is a basic QuickServer that can handle up to 250 points and an enhanced QuickServer that can handle 500 points.

The FS-QS-1220 Series is preloaded with two BAS drivers (one RS485 serial port, one RS232 serial port, and one Ethernet port) Drivers from a list of over 150 protocols. Each QuickServer can handle up to 500 points.

Each QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

BTL Mark is registered to the MSA BACnet Driver for MSA QuickServer line of products

Quickserver Gateway (Serial-Ethernet)

The QuickServer is a high performance, fully configurable, cost effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators world-wide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

QuickServer (Serial-Ethernet) is available in two series:

The QuickServer FS-QS-2X10 series is available at four different point capacities. Each QuickServer is preloaded with two drivers (serial and/or Ethernet) from a customer’s choice of 140 different drivers, E.G. Modbus, BACnet, SNMP, EtherNet/IP and many more.

The FS-QS-2010 with 2 RS485 and 1 ethernet port can support up to 250 points. The FS-QS-2210 can support up to 500 points. The FS-QS-2310 can support up to 3,000 points. The FS-QS-2410 can support up to 5,000 points.

Equivalently the FS-QS-2020 with 1 RS485, 1 RS232 and 1 ethernet port can support up to 250 points. The FS-QS-2220 can support up to 500 points. The FS-QS-2320 can support up to 3,000 points. The FS-QS-2420 can support up to 5,000 points.

Every QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

BTL Mark is registered to the MSA BACnet Driver for MSA QuickServer line of products

Dual Ethernet Port Quickserver Gateway (Serial-Ethernet)

The QuickServer is a high performance, fully configurable, cost effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators world-wide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

The QuickServer FS-QS-3X10-F series is available at four different point capacities. Each QuickServer is preloaded with 140 different drivers, such as Modbus, BACnet, SNMP, EtherNet/IP and many more. See page 3 for the complete list. The FS-QS-3010-F can support up to 250 points. The FS-QS-3110-F can support up to 500 points. The FS-QS-3210-F can support up to 1,000 points. The FS-QS-3310-F can support up to 3,000 points. The FS-QS-3410-F can support up to 5,000 points. The FS-QS-3510-Fire can support up to 10,000 points.

With two Ethernet ports, the QuickServer allows data to move seamlessly across disparate subnets, using a dedicated port for Cloud connectivity. This port isolation allows for enhanced LAN security from the BMS/WAN/Cloud. An embedded OpenVPN Server enables secure remote access to Ethernet devices in the field.

Every QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

BTL Mark is registered to the MSA BACnet Driver for MSA QuickServer line of products

Notifier ONYX NFS-640 (NFS-640, NFS2-640 and NFS-320)

The NFS-640 Serial driver allows the FieldServer to record data from Notifier Onyx Series NFS-640, NFS2-640 and NFS-320 Fire Panels over RS-232. The FieldServer primarily acts as a Passive Client receiving unsolicited messages and updating the status of a Notifier Fire Alarm Panel.

The main purpose of this driver is to record the status of Fire Alarm System detectors and modules in a bit oriented Data Array. It is limited by the information that the Notifier Panel broadcasts in the form of text messages through its RS-232 communication port. The accuracy and timeliness of the data is therefore limited by the frequency of update messages that the Notifier Fire Panel issues.

The types of Notifier messages supported by this driver are summarized in Appendix C.1 of the manual. A detailed table showing each type of panel message the FieldServer recognizes and the effect that it has on the status of points in the data array is presented in Appendix C.2 of the manual. The device status to the data array mapping is also provided in Appendix C.2 of the manual.

It is possible to connect through the CRT Port., however the use of this port restricts the use of Notifier Networking, thus a fire panel connected to a Noti-Fire-Net will not be supported. If the CRT port is used, the FieldServer can actively request the status of all points, devices and zones on a periodic basis. This status request is configurable from 5minutes with no upper bounds. Note that communication through this port does not equate to Port Supervision. Refer to Appendix A.1 of the Manual.

The panel must output messages in English. For Notifier 640 Onyx firmware with Spanish firmware (as sold in Mexico and other Central and South American markets) please refer to the fact sheet ‘FST_DFS_Notifier_NFS-640 (Onyx)(Spanish)’

I'd like to inquire about the Notifier Onyx 640 to BACnet IP QuickServer Gateway FS-QS-XXX0-0342. Please provide me with a quote for this product.

Specifications

Classic QuickServer Gateway (Serial-Ethernet)
Classic QuickServer Specs: FS-QS-1XX0

Depending on what hardware you require, the specifications will contain different options. For Example, M-bus section is only available on the FS-QS-1x50/FS-QS-1x51 devices where x is A for 16 devices, B for 32 devices and C for 64 devices. See images below for Port Support and product code check.




Quickserver Gateway (Serial-Ethernet)
QuickServer Specs: FS-QS-2XX0

Environment
  • Operating Temperature: -20 to 70°C (-4 to 158oF)
  • Relative Humidity: 10-95% RH non-condensing
Power Requirements
  • Intput: 24VAC 0.125A, 12-24VDC 0.25A @12 VDC
  • Max Power: 3W


Physical Dimensions
  • Dimensions (WxDxH): 4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8cm)
  • Weight: 0.4 lbs (0.2 Kg)
Other

Web configuration
On-board diagnostics
DIN rail mount included

  • Capacity: 250 points FS-QS-20XX, 500 points FS-QS-22XX, 3000 points FS-QS-23XX, 5000 points FS-QS-24XX
Communication

FS-QS-2XX0

  • Baud: 9600, 19200, 34800, 57600, 76800
  • Serial (Galvanic Isolation) Ports: 1 x RS485, 1 x RS232/RS485
  • Ethernet Port: 10/100baseT, MDIX, DHCP

Approvals
  • UL 60950
  • IC Canada
  • RoHS Compliant
  • WEEE compliant
  • RoHS compliant
  • CE and FCC class B and C part 15

Dual Ethernet Port Quickserver Gateway (Serial-Ethernet)
Dual Ethernet Port QuickServers: FS-QS-3XX0

Environment

  • Operating Temperature: -20 to 70°C (-4 to 158°F)
  • Relative Humidity: 10-95% RH non-condensing

Power Requirements

  • Input: 24VAC 0.125A, 9-30VDC 0.25A @12 VDC
  • Max Power: 3W

Physical Dimensions

  • Dimensions (WxDxH): 4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8cm)
  • Weight: 0.4 lbs (0.2 Kg)

Other

Web configuration
On-board diagnostics
DIN rail mount included

Communication

FS-QS-3XX0

  • Baud: 9600, 19200, 38400, 57600, 76800, 115000
  • Serial (Galvanic Isolation): 1 x RS-485/RS-232 & 1 x RS-485
  • Ethernet: 2 x 10/100BaseT, MDIX, DHCP

Approvals

  • CE and FCC Class B & C Part 15
  • BTL Marked
  • UL 60950-1 and CAN/CSA C22 2
  • IC Canada & KC Certification
  • RoHS3 and WEEE complaint

Block Diagrams

BACnet Combined Block DiagramNotifier Gateway Connections Block Diagram