FS-8700-01 – Modbus RTU

Description

The Modbus RTU driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using Modbus RTU protocol. The FieldServer is capable of being used as a port expander.

The FieldServer can emulate either a Server or Client. The FieldServer is capable of supporting devices that use two Modbus Registers to transfer IEEE floating point format.

Fieldserver ModeNodesComments
Client1Only 1 client node allowed on Multidrop systems
Server255Actual electrical loading may reduce number of usable server nodes

Formal Driver Type

  • Serial
  • Client or Server

Compatibility Matrix

FieldServer ModelCompatible with this driver
FS-x2010Yes
FS-x2011Yes
FS-x40Yes
FS-x30Yes

Connection Information

Connection type:RS-232 or RS-485 (Two wire, Half-Duplex)
Baud Rates:110-11520
Data Bits:8
Stop Bits:1
Parity:None
Multidrop Capability:Yes

Devices tested

DeviceTested (FACTORY, SITE)
Modbus RTU DevicesFactory
Liebert SitelinkCustomer
Square D Activar 58Customer
TriatekCustomer
WonderWare InTouchFactory
Fix IntellutionFactory
GE CimplicityCustomer
ModscanFactory
GE PLEPMFactory
ABB ExtrelCustomer
Andover ControlsCustomer
Eurotherm ChesselCustomer
Sierra Monitor SentryFactory
MagnatekCustomer
OthersPlease contact Factory

Connection configurations

Communications functions – Supported functions at a glance:

Function Codes Supported:

Function CodesDescription
01Read Discrete Output Status (0xxxx)
02Read Discrete Input Status (1xxxx)
03Read Output Registers (4xxxx)
04Read Input Registers (3xxxx)
05Force Single Coil (0xxxx)
06Preset Single Register (4xxxx)
15Force Multiple Coils (0xxxx)
16Preset Multiple Registers (4xxxx)

Gateway Selector

Select your combination of protocols.
Protocol 1
Protocol 2