Veeder-Root - Can you show me an example of typical FieldServer / QuickServer Veeder Lonworks points

DO NOT USE THIS DATA – IT IS SUBJECT TO CHANGE AND IS PROVIDED FOR REFERENCE ONLY. The points listed and the Lonworks addresses allocated are typical. We strongly advise you not to hand this to the contractor implementing the Lonworks Client. They should use the actual map provided for your project.


// !!!!!!!!!!!! Ignore SNVT_Index = Data will change        
         
Map_Descriptors        
Map_Descriptor_Name                  Data_Array_Name  Data_Array_OffsetNode_Name      FunctionLon_Function SNVT_Index SNVT_Type     SNVT_Option
nviAlarmReset                        VEED_DA_RESET    0Virtual_Veeder Server  NVUI         1SNVT_switch   state
nviStartLeakTst                      VEED_DA_START    0Virtual_Veeder Server  NVUI         2SNVT_switch   state
nviStopLeakTest                      VEED_DA_STOP     0Virtual_Veeder Server  NVUI         3SNVT_switch   state
         
// Inventory Data - Sample of points for Tank 3 and 4        
Map_Descriptors        
Map_Descriptor_Name                  Data_Array_Name Data_Array_OffsetNode_Name      FunctionLon_Function SNVT_Index SNVT_Type       SNVT_Option
nvoT3_ProdCode                       VEED_DA_INVENT3 0Virtual_Veeder wrbx    NVUOIMX      301SNVT_count_f    -
nvoT3_TankStatus                     VEED_DA_INVENT3 1Virtual_Veeder wrbx    NVUOIMX      302SNVT_count_f    -
nvoT3_Volume                         VEED_DA_INVENT3 2Virtual_Veeder wrbx    NVUOIMX      303SNVT_vol_f      -
nvoT3_TC_Volume                      VEED_DA_INVENT3 3Virtual_Veeder wrbx    NVUOIMX      304SNVT_vol_f      -
nvoT3_Ullage                         VEED_DA_INVENT3 4Virtual_Veeder wrbx    NVUOIMX      305SNVT_length_mil -
nvoT3_Height                         VEED_DA_INVENT3 5Virtual_Veeder wrbx    NVUOIMX      306SNVT_length_mil -
nvoT3_Water                          VEED_DA_INVENT3 6Virtual_Veeder wrbx    NVUOIMX      307SNVT_length_mil -
nvoT3_Temp                           VEED_DA_INVENT3 7Virtual_Veeder wrbx    NVUOIMX      308SNVT_temp_f     -
nvoT3_WaterVol                       VEED_DA_INVENT3 8Virtual_Veeder wrbx    NVUOIMX      309SNVT_vol_f      -
nvoT4_ProdCode                       VEED_DA_INVENT4 0Virtual_Veeder wrbx    NVUOIMX      401SNVT_count_f    -
nvoT4_TankStat                       VEED_DA_INVENT4 1Virtual_Veeder wrbx    NVUOIMX      402SNVT_count_f    -
nvoT4_Volume                         VEED_DA_INVENT4 2Virtual_Veeder wrbx    NVUOIMX      403SNVT_vol_f      -
nvoT4_TC_Volume                      VEED_DA_INVENT4 3Virtual_Veeder wrbx    NVUOIMX      404SNVT_Index      -
nvoT4_Ullage                         VEED_DA_INVENT4 4Virtual_Veeder wrbx    NVUOIMX      405SNVT_length_mil -
nvoT4_Height                         VEED_DA_INVENT4 5Virtual_Veeder wrbx    NVUOIMX      406SNVT_length_mil -
nvoT4_Water                          VEED_DA_INVENT4 6Virtual_Veeder wrbx    NVUOIMX      407SNVT_length_mil -
nvoT4_Temp                           VEED_DA_INVENT4 7Virtual_Veeder wrbx    NVUOIMX      408SNVT_temp_f     -
nvoT4_WaterVol                       VEED_DA_INVENT4 8Virtual_Veeder wrbx    NVUOIMX      409SNVT_vol_f      -
         
         
// Vacuum Sensor SNVT's - Sample of points for vacuum sensor #1       
nvoU1_SerialNum            VEED_DA_VACUUM1 2Virtual_Veeder wrbx    NVUOIMX      1002SNVT_count_f -
nvoU1_EvacState            VEED_DA_VACUUM1 3Virtual_Veeder wrbx    NVUOIMX      1003SNVT_count_f -
nvoU1_FluidStat            VEED_DA_VACUUM1 4Virtual_Veeder wrbx    NVUOIMX      1004SNVT_count_f -
nvoU1_CtrlVlv              VEED_DA_VACUUM1 5Virtual_Veeder wrbx    NVUOIMX      1005SNVT_count_f -
nvoU1_ValidLR              VEED_DA_VACUUM1 6Virtual_Veeder wrbx    NVUOIMX      1007SNVT_count_f -
nvoU1_LeakRatee            VEED_DA_VACUUM1 8Virtual_Veeder wrbx    NVUOIMX      1008SNVT_count_f -
nvoU1_LeakRatex            VEED_DA_VACUUM1 9Virtual_Veeder wrbx    NVUOIMX      1009SNVT_count_f -
nvoU1_ValidTime            VEED_DA_VACUUM1 10Virtual_Veeder wrbx    NVUOIMX      1010SNVT_count_f -
nvoU1_TimeNoVac            VEED_DA_VACUUM1 12Virtual_Veeder wrbx    NVUOIMX      1002SNVT_count_f -
nvoU1_ValidER              VEED_DA_VACUUM1 13Virtual_Veeder wrbx    NVUOIMX      1003SNVT_count_f -
nvoU1_EvacRatio            VEED_DA_VACUUM1 15Virtual_Veeder wrbx    NVUOIMX      1015SNVT_count_f -
nvoU1_EvacRatiox           VEED_DA_VACUUM1 16Virtual_Veeder wrbx    NVUOIMX      1016SNVT_count_f -
nvoU1_ER_Press             VEED_DA_VACUUM1 17Virtual_Veeder wrbx    NVUOIMX      1017SNVT_count_f -
nvoU1_ER_pressx            VEED_DA_VACUUM1 18Virtual_Veeder wrbx    NVUOIMX      1018SNVT_count_f -
nvoU1_FaultBits            VEED_DA_VACUUM1 19Virtual_Veeder wrbx    NVUOIMX      1019SNVT_count_f -
nvoU1_NumValues            VEED_DA_VACUUM1 20Virtual_Veeder wrbx    NVUOIMX      1020SNVT_count_f -
nvoU1_CompnstdP            VEED_DA_VACUUM1 21Virtual_Veeder wrbx    NVUOIMX      1021SNVT_count_f -
nvoU1_CompnstdPx           VEED_DA_VACUUM1 22Virtual_Veeder wrbx    NVUOIMX      1022SNVT_count_f -
nvoU1_UncompP              VEED_DA_VACUUM1 23Virtual_Veeder wrbx    NVUOIMX      1023SNVT_count_f -
nvoU1_UncompPx             VEED_DA_VACUUM1 24Virtual_Veeder wrbx    NVUOIMX      1024SNVT_count_f -
         
                                             
// System Alarms  - present in all systems        
nvoSys_Normal               VEED_DA_101     0Virtual_Veeder wrbx    NVUOIMX      10000SNVT_switch   state
nvoSys_SysAlm               VEED_DA_S1      1Virtual_Veeder wrbx    NVUOIMX      10001SNVT_switch   state
nvoSys_TankAlm              VEED_DA_S1      2Virtual_Veeder wrbx    NVUOIMX      10002SNVT_switch   state
nvoSys_LiqSens              VEED_DA_S1      3Virtual_Veeder wrbx    NVUOIMX      10003SNVT_switch   state
nvoSys_VapSens              VEED_DA_S1      4Virtual_Veeder wrbx    NVUOIMX      10004SNVT_switch   state
nvoSys_InputAlm             VEED_DA_S1      5Virtual_Veeder wrbx    NVUOIMX      10005SNVT_switch   state
nvoSys_VolLine              VEED_DA_S1      6Virtual_Veeder wrbx    NVUOIMX      10006SNVT_switch   state
nvoSys_Gwater               VEED_DA_S1      7Virtual_Veeder wrbx    NVUOIMX      10007SNVT_switch   state
nvoSys_Typea                VEED_DA_S1      8Virtual_Veeder wrbx    NVUOIMX      10008SNVT_switch   state
nvoSys_Typeb                VEED_DA_S1      12Virtual_Veeder wrbx    NVUOIMX      10001SNVT_switch   state
nvoSys_Universal            VEED_DA_S1      13Virtual_Veeder wrbx    NVUOIMX      10013SNVT_switch   state
nvoSys_AutoDial             VEED_DA_S1      14Virtual_Veeder wrbx    NVUOIMX      10014SNVT_switch   state
nvoSys_MechDisp             VEED_DA_S1      18Virtual_Veeder wrbx    NVUOIMX      10018SNVT_switch   state
nvoSys_ElecDisp             VEED_DA_S1      19Virtual_Veeder wrbx    NVUOIMX      10019SNVT_switch   state
nvoSys_ProdAlm              VEED_DA_S1      20Virtual_Veeder wrbx    NVUOIMX      10020SNVT_switch   state
nvoSys_PressLeak            VEED_DA_S1      21Virtual_Veeder wrbx    NVUOIMX      10021SNVT_switch   state
nvoSys_WPLLD                VEED_DA_S1      26Virtual_Veeder wrbx    NVUOIMX      10026SNVT_switch   state
nvoSys_External             VEED_DA_S1      99Virtual_Veeder wrbx    NVUOIMX      10099SNVT_switch   state
                    
// Tank Alarms - Sample is points for Tank #3        
nvoT3_AnyAlm                         VEED_DA_T3     0Virtual_Veeder wrbx    NVUOIMX      203000SNVT_switch   state
nvoT3_SetupWarn                      VEED_DA_T3     1Virtual_Veeder wrbx    NVUOIMX      203001SNVT_switch   state
nvoT3_LeakAlm                        VEED_DA_T3     2Virtual_Veeder wrbx    NVUOIMX      203002SNVT_switch   state
nvoT3_HiWaterAlm                     VEED_DA_T3     3Virtual_Veeder wrbx    NVUOIMX      203003SNVT_switch   state
nvoT3_Overfill                       VEED_DA_T3     4Virtual_Veeder wrbx    NVUOIMX      203004SNVT_switch   state
nvoT3_LoProduct                      VEED_DA_T3     5Virtual_Veeder wrbx    NVUOIMX      203005SNVT_switch   state
nvoT3_SuddenLos                      VEED_DA_T3     6Virtual_Veeder wrbx    NVUOIMX      203006SNVT_switch   state
nvoT3_HiProduct                      VEED_DA_T3     7Virtual_Veeder wrbx    NVUOIMX      203007SNVT_switch   state
nvoT3_InvalidFL                      VEED_DA_T3     8Virtual_Veeder wrbx    NVUOIMX      203008SNVT_switch   state
nvoT3_ProbeOut                       VEED_DA_T3     9Virtual_Veeder wrbx    NVUOIMX      203009SNVT_switch   state
nvoT3_HiWaterWrn                     VEED_DA_T3     10Virtual_Veeder wrbx    NVUOIMX      203010SNVT_switch   state
nvoT3_DeliverWrn                     VEED_DA_T3     11Virtual_Veeder wrbx    NVUOIMX      203011SNVT_switch   state
nvoT3_MaxProd                        VEED_DA_T3     12Virtual_Veeder wrbx    NVUOIMX      203012SNVT_switch   state
nvoT3_GrossLeak                      VEED_DA_T3     13Virtual_Veeder wrbx    NVUOIMX      203013SNVT_switch   state
nvoT3_PeriodLeak                     VEED_DA_T3     14Virtual_Veeder wrbx    NVUOIMX      203014SNVT_switch   state
nvoT3_AnnualLeak                     VEED_DA_T3     15Virtual_Veeder wrbx    NVUOIMX      203015SNVT_switch   state
nvoT3_PeriodWrn                      VEED_DA_T3     16Virtual_Veeder wrbx    NVUOIMX      203016SNVT_switch   state
nvoT3_AnnualWrn                      VEED_DA_T3     17Virtual_Veeder wrbx    NVUOIMX      203017SNVT_switch   state
nvoT3_PeriodAlm                      VEED_DA_T3     18Virtual_Veeder wrbx    NVUOIMX      203018SNVT_switch   state
nvoT3_AnnualAlm                      VEED_DA_T3     19Virtual_Veeder wrbx    NVUOIMX      203019SNVT_switch   state
nvoT3_LeakTest                       VEED_DA_T3     20Virtual_Veeder wrbx    NVUOIMX      203020SNVT_switch   state
nvoT3_NoCSLD                         VEED_DA_T3     21Virtual_Veeder wrbx    NVUOIMX      203021SNVT_switch   state
nvoT3_Siphon                         VEED_DA_T3     22Virtual_Veeder wrbx    NVUOIMX      203022SNVT_switch   state
nvoT3_CSLDRate                       VEED_DA_T3     23Virtual_Veeder wrbx    NVUOIMX      203023SNVT_switch   state
nvoT3_AccuChart                      VEED_DA_T3     24Virtual_Veeder wrbx    NVUOIMX      203024SNVT_switch   state
nvoT3_HRMWarn                        VEED_DA_T3     25Virtual_Veeder wrbx    NVUOIMX      203025SNVT_switch   state
nvoT3_HRMAlm                         VEED_DA_T3     26Virtual_Veeder wrbx    NVUOIMX      203026SNVT_switch   state
nvoT3_ColdWarn                       VEED_DA_T3     27Virtual_Veeder wrbx    NVUOIMX      203027SNVT_switch   state
nvoT3_Missing                        VEED_DA_T3     28Virtual_Veeder wrbx    NVUOIMX      203028SNVT_switch   state
         
// Liquid Sensor Alarms - Sample is for Lquid Sensor #1       
nvoL1_AnyAlm                    VEED_DA_L1     0Virtual_Veeder wrbx    NVUOIMX      401000SNVT_switch   state
nvoL1_SetupWarn                 VEED_DA_L1     2Virtual_Veeder wrbx    NVUOIMX      401002SNVT_switch   state
nvoL1_FuelAlm                   VEED_DA_L1     3Virtual_Veeder wrbx    NVUOIMX      401003SNVT_switch   state
nvoL1_OutAlm                    VEED_DA_L1     4Virtual_Veeder wrbx    NVUOIMX      401004SNVT_switch   state
nvoL1_ShortAlm                  VEED_DA_L1     5Virtual_Veeder wrbx    NVUOIMX      401005SNVT_switch   state
nvoL1_WaterAlm                  VEED_DA_L1     6Virtual_Veeder wrbx    NVUOIMX      401006SNVT_switch   state
nvoL1_WaterOut                  VEED_DA_L1     7Virtual_Veeder wrbx    NVUOIMX      401007SNVT_switch   state
nvoL1_HiLiqAlm                  VEED_DA_L1     8Virtual_Veeder wrbx    NVUOIMX      401008SNVT_switch   state
nvoL1_LoLiqAlm                  VEED_DA_L1     9Virtual_Veeder wrbx    NVUOIMX      401009SNVT_switch   state
nvoL1_LiqWarn                   VEED_DA_L1     10Virtual_Veeder wrbx    NVUOIMX      401010SNVT_switch   state
         
         
// Vapor Sensor Alarms - Sample is for Vapor Sensor #1       
nvoV1_AnyAlm                    VEED_DA_V1     0Virtual_Veeder wrbx    NVUOIMX      401000SNVT_switch   state
nvoV1_SetupWarn                 VEED_DA_V1     2Virtual_Veeder wrbx    NVUOIMX      401002SNVT_switch   state
nvoV1_FuelAlm                   VEED_DA_V1     3Virtual_Veeder wrbx    NVUOIMX      401003SNVT_switch   state
nvoV1_OutAlm                    VEED_DA_V1     4Virtual_Veeder wrbx    NVUOIMX      401004SNVT_switch   state
nvoV1_ShortAlm                  VEED_DA_V1     5Virtual_Veeder wrbx    NVUOIMX      401005SNVT_switch   state
nvoV1_WaterAlm                  VEED_DA_V1     6Virtual_Veeder wrbx    NVUOIMX      401006SNVT_switch   state
nvoV1_WaterOut                  VEED_DA_V1     7Virtual_Veeder wrbx    NVUOIMX      401007SNVT_switch   state
nvoV1_HiLiqAlm                  VEED_DA_V1     8Virtual_Veeder wrbx    NVUOIMX      401008SNVT_switch   state
nvoV1_LoLiqAlm                  VEED_DA_V1     9Virtual_Veeder wrbx    NVUOIMX      401009SNVT_switch   state
nvoV1_LiqWarn                   VEED_DA_V1     10Virtual_Veeder wrbx    NVUOIMX      401010SNVT_switch   state
         


XIF File

Download the file

File: fserver-25.xif generated by LonDriver Revision 1.26(a), XIF Version 4.0

Copyright (c) 2000-2005 by FieldServer Technologies

All Rights Reserved. Run on Wed Jul 28 06:58:51 2010

90:00:95:47:1E:02:04:F6

2 15 1 108 0 14 11 3 3 12 14 11 11 11 11 3 0 16 63 0 1 11 108

0 5 7 13 28 0 0 15 5 3 109 63

1 7 1 0 4 4 4 15 200 0

78125 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 1 5 8 5 12 14 15

*

"Veeder Demo Rev5

VAR nviAlarmReset 0 0 0 0

0 1 63 0 0 0 0 0 0 0 0 0 0

*

95 * 2

1 0 0 0 0

1 0 0 1 0

VAR nviStartLeakTst 1 0 0 0

0 1 63 0 0 0 0 0 0 0 0 0 0

*

95 * 2

1 0 0 0 0

1 0 0 1 0

VAR nviStopLeakTest 2 0 0 0

0 1 63 0 0 0 0 0 0 0 0 0 0

*

95 * 2

1 0 0 0 0

1 0 0 1 0

VAR nvoT3_ProdCode 3 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_TankStatus 4 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Volume 5 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_TC_Volume 6 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Ullage 7 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Height 8 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Water 9 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Temp 10 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_WaterVol 11 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_ProdCode 12 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_TankStat 13 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Volume 14 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_TC_Volume 15 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Ullage 16 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Height 17 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Water 18 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Temp 19 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_WaterVol 20 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_SerialNum 21 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_EvacState 22 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_FluidStat 23 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_CtrlVlv 24 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ValidLR 25 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_LeakRatee 26 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_LeakRatex 27 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ValidTime 28 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_TimeNoVac 29 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ValidER 30 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_EvacRatio 31 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_EvacRatiox 32 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ER_Press 33 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ER_pressx 34 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_FaultBits 35 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_NumValues 36 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_CompnstdP 37 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_CompnstdPx 38 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_UncompP 39 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_UncompPx 40 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Normal 41 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_SysAlm 42 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_TankAlm 43 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_LiqSens 44 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_VapSens 45 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_InputAlm 46 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_VolLine 47 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Gwater 48 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Typea 49 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Typeb 50 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Universal 51 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_AutoDial 52 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_MechDisp 53 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_ElecDisp 54 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_ProdAlm 55 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_PressLeak 56 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_WPLLD 57 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_External 58 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnyAlm 59 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_SetupWarn 60 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_LeakAlm 61 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HiWaterAlm 62 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Overfill 63 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_LoProduct 64 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_SuddenLos 65 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HiProduct 66 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_InvalidFL 67 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_ProbeOut 68 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HiWaterWrn 69 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_DeliverWrn 70 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_MaxProd 71 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_GrossLeak 72 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_PeriodLeak 73 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnnualLeak 74 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_PeriodWrn 75 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnnualWrn 76 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_PeriodAlm 77 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnnualAlm 78 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_LeakTest 79 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_NoCSLD 80 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Siphon 81 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_CSLDRate 82 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AccuChart 83 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HRMWarn 84 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HRMAlm 85 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_ColdWarn 86 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Missing 87 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_AnyAlm 88 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_SetupWarn 89 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_FuelAlm 90 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_OutAlm 91 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_ShortAlm 92 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_WaterAlm 93 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_WaterOut 94 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_HiLiqAlm 95 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_LoLiqAlm 96 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_LiqWarn 97 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_AnyAlm 98 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_SetupWarn 99 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_FuelAlm 100 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_OutAlm 101 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_ShortAlm 102 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_WaterAlm 103 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_WaterOut 104 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_HiLiqAlm 105 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_LoLiqAlm 106 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_LiqWarn 107 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0


Gateway Selector

Select your combination of protocols.
Protocol 1
Protocol 2

Contact Us

Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

*Required Field
I'd like to receive the newsletter. *Check email for confirmation.
*Required Field
Preferred Time To Be Contacted (PST)
8:00am - 12:00pm 12:00pm - 5:00pm