FS-8700-19 – Metasys N2 by JCI

FieldServer Driver – SerialFS-8700-19Metasys N2 by JCI

Description

The Metasys N2 by JCI network supports communications with a diverse range of devices. Many N2 compatible devices use their own flavor of the protocol. The different flavors are designed to co-exist on the same N2 network. Care must be taken to ensure the device of interest is covered by the FieldServer implementation.

At present the FieldServer Metasys N2 by JCI driver will support communications with the following devices or classes of devices when acting as a client:

  1. N2Open-compliant devices. N2Open is a published N2-compatible protocol enabling 3rd party device vendors to integrate with N2.
  2. VMA 1400 series (with restrictions, see below)
  3. DX9100 and XT9100

When acting as a server the FieldServer Metasys N2 by JCI driver can emulate an N2Open device only.

Fieldserver ModeNodesComments
Client1Only 1 client node allowed on Multidrop systems. Can communicate with:
  • N2Open
  • VMA 1400 series (AI,BI,AO,BO and custom types)
  • DX9100 / XT9100
Server255Number of nodes limited by N2 address space. Can only act as a N2Open server node.

Formal Driver Type

  • Serial
  • Client or Server

Connection Information

Connection type:RS-485 (Two wire, Half-Duplex)
Baud Rates:9600 (N2 standard)
Data Bits:8
Stop Bits:1
Parity:None
Multidrop Capability:Yes

Devices tested

DeviceSupportedTested (FACTORY, SITE)N2Open Device
UNTYes.pngSiteYes.png
VMA1410, VMA1420Yes.pngFactory and Site
DX9100 with XT9100 extensionYes.pngFactory and Site
LCP/DX9100No.pngnot tested
NCM (FieldServer as N2Open server)Yes.pngFactory and SiteYes.png
VAVYes.pngSiteYes.png
AHUYes.pngnot testedYes.png
VNDYes.pngnot testedYes.png
PHXConsult Factorynot testedConsult Factory
MIGConsult Factorynot testedConsult Factory
ILCConsult Factorynot testedConsult Factory
IFCConsult Factorynot testedConsult Factory
TC-9100Consult Factorynot testedConsult Factory
TEC1000Consult Factorynot testedConsult Factory

Connection configurations

8700-19-connection.jpg

Connection Notes

Only one N2 client may be connected to a N2 network. If the FieldServer is to act as a client, ensure no other clients are connected to the same N2 network. In the Interceptor Mode the FieldServer can be installed between an existing N2 host and the remainder of the N2 network. It will then intercept the data, and is also able to interleave its own polls for data items not configured in the host in the time between polls sent by the host

Communications functions – Supported functions at a glance:

Function Codes Supported – N2Open:

FieldServer Data TypeDescription (or Device Data Type)
Analog_InputAnalog Input (AI)
Digital_InputBinary Input (BI)
Analog_OutputAnalog Output (AO)
Digital_OutputBinary Output (BO)
Float_RegInternal Float value (ADF)
IntegerInternal Integer value (ADI)
ByteInternal Byte value (BD)

Read Operations Supported – N2Open

FieldServer as a ClientFieldServer as a Server
Read Current Value (all data types)Read Current Value (all data types)
direct read, Change-of-State (COS) polldirect read, Change-of-State (COS) poll
Read Attribute (all data types):Read Attribute (all data types):
direct read, specifying a legal attribute numberdirect read, specifying a legal attribute number direct read, specifying a legal attribute number
Identify Self command

Write (Control) Operations Supported – N2Open

FieldServer as a ClientFieldServer as a Server
Override Current Value (all data types) implemented as Write on FieldServerOverride Current Value (all data types) implemented as Write on FieldServer
Override Release (all data types)Override Release (all data types)
Write Attribute (all data types) direct write, specifying a legal attribute numberWrite Attribute (all data types) direct write, specifying a legal attribute number

Listing of Supported Attributes – N2Open

Data TypeAttribute No.Attribute
Analog Input1Object Configuration
2Object Status
3Analog Input Value
4Low Alarm Limit
5High Alarm Limit
6Low Warn Limit
7High Warn Limit
8Differential
Binary Input1Object Configuration
2Object Status
Analog Output1Object Configuration
2Object Status
3Current Value
Binary Output1Object Configuration
2Object Status
3Minimum On-Time
4Minimum Off-Time
5Maximum Cycles/Hour
Internal Float1Object Status
2Current Value
Internal Integer1Object Status
2Current Value
Internal Byte1Object Status
2Current Value

Unsupported Functions and Data Types – N2Open

FunctionReason
Time UpdateNot required
Read Memory DiagnosticsNot required
Warm Start MessageNot required
Status Update MessageNot required
Programming messages (upload, download)FieldServer is a data transfer device, and as such, programming messages are not required

Data Types Supported – VMA

FieldServer Data TypeDescription (or Device Data Type)
Analog_InputAnalog Input (AI)
Digital_InputBinary Input (BI)
Analog_OutputAnalog Output (AO)
Digital_OutputBinary Output (BO)
Float_RegInternal Float value (ADF)
IntegerInternal Integer value (ADI)
ByteInternal Byte value (BD)

Read Operations Supported – VMA

FieldServer as a ClientFieldServer as a Server
Read Current Value (all data types)Not applicable
Direct Read, Change-of-State (COS) poll

Write (control) Operations Supported – VMA

FieldServer as a ClientFieldServer as a Server
Write / Override Current Value (all data types) implemented as Write on FieldServerNot applicable
Override Release (AI and BI only) use writes for outputs and internal values

Unsupported Functions and Data Types – VMA

FunctionReason
Programming messages (upload, download)FieldServer is a data transfer device, and as such, programming messages are not required. Note that the Interceptor Mode will not allow the field devices to be programmed through the FieldServer.

Data Types Supported – DX9100

FieldServer Data TypeDescription (or Device Data Type)
Not specified for DX9100 device typeSupported sections of Address Map:
general control module
programmable modules 1-12
analog input modules 1-8
analog output modules 1-2
digital output modules 3-8
extension modules 1-8
time schedules 1-8
optimal start/stop modules 1-2
analog output modules 9-10
auxiliary analog output modules 11-13

Read Operations Supported – DX9100

FieldServer as a ClientFieldServer as a Server
Read of all points supportedNot applicable

Write (control) Operations Supported – DX9100

FieldServer as a ClientFieldServer as a Server
Write of all points supportedNot applicable
DX9100 may not allow writes to specific values

Unsupported Functions and Data Types – DX9100

FunctionReason
Programming messagesFieldServer is a data transfer device, and as such, programming messages are not required

Metasys® as used in this document is a trademark of Johnson Controls, Inc.