FS-8700-30 – YorkTalk

FieldServer Driver – Serial 
FS-8700-30
YorkTalk

Driver Code:SPEC
Version:1.00

 

Device Options:

  1. York Translator – The recommended option: A direct RS232 connection is made to the chiller. This is a very cost effective option as a single FieldServer can support 8 simultaneous connection support 8 simultaneous connections. The aggregate bandwidth is then also 8 times higher than in the case of a single multidrop connection to 8 devices.
  2. XL Translator – A RS232 connection is made to the XL Translator (also known as ISN LDC 17 – Link Data Controller), which in turn communicates with York devices via RS485. For this configuration, the York Chillers must be fitted with the "Linc Chiller" module to allow compatibility with the LDC's RS485 network.
  3. MicroGateway – A RS232 connection is made to the MicroGateway, which in turn communicates with York devices via RS485. For this configuration, the York Chillers must be fitted with the "Linc Chiller" module to allow compatibility with the LDC's RS485 network.

 

Map of the FieldServer Yorktalk Client driver (XL Translator, York Translator)

8051 addressYork Talk Block (feature, section)York Talk LineRead/WriteComment
0 -> 81f02s01P01 -> P81Read OnlyRead chiller status of length 82. Any single point can be read, or sub_blocks of any inclusive address range can be read.
82f01s01P01Read or WriteFirst set_point.
83f01s02P01Read or WriteSecond set_point block.
84f01s02P02Read or WriteSame as above
85nonenoneRead or WriteEnumerated York_Talk Client state machine error code. 0.0 means none. Write will clear
86nonenoneRead or WriteYork Talk returned error code. 0.0 means none. Will contain last logged error. Write will clear.

 

Notes (XL Translator, York Translator):

The following combinations can be read:

  • 0-81 or any subset thereof
  • 82 by itself
  • 83-84 or any subset thereof
  • 85 by itself
  • 86 by itself

The following combinations can be written to:

  • 82 by itself. Only the value 0.0 (OFF) and 1.0 (ON)
  • 83 by itself
  • 84 by itself
  • 85 by itself. Will reset latched error code to 0.0
  • 86 by itself. Will reset latched error code to 0.0

The system is offset sensitive allowing single data blocks but multiple scan blocks.

 

Map of the FieldServer Yorktalk Client driver (MicroGateway)

The MicroGateway mode allows the f, s and p parameters (feature, section and page) to be specified directly for write messages, allowing all single-value fields (such as set points and digital outputs) to be written. For read messages, only f54 is available, but the section (s parameter) can be specified as required to address different devices.