CAS Gateway Firmware Upgrade Instructions

Firmware Update Instructions for a CAS Gateway Device

This article provides step-by-step instructions for upgrading the firmware on a CAS Gateway device using Chipkin’s CAS Gateway AutoUpdate tool. The process is typically performed on a local network, where your PC and the CAS Gateway are connected to the same network segment so the tool can discover the device and transfer the firmware file.

If you are updating firmware as part of troubleshooting, commissioning, or scheduled maintenance, it is recommended to plan the update for a suitable maintenance window. A firmware update may take a few minutes to complete, and the device may reboot at the end of the process.

Before You Start

  • You will need a PC connected to the same network as the CAS Gateway.
  • You will need the CAS Gateway AutoUpdate tool installed on your PC.
  • You will need the correct firmware file for your CAS Gateway.
  • Ensure network connectivity (for example, confirm the CAS Gateway Ethernet port link light is illuminated).

Important: Use only firmware provided by CAS/Chipkin for your specific device and purpose. Do not upload other firmware files unless explicitly instructed to do so by Chipkin Automation Systems support.

Step-by-Step: Upgrade Firmware Using CAS Gateway AutoUpdate

  1. Download and install the CAS Gateway AutoUpdate tool.
  2. Connect the CAS Gateway Ethernet port to your network.
    • Ensure the CAS Gateway Ethernet port “link” light illuminates, showing a connection to the network.
  3. Connect your PC to the same network that the CAS Gateway is connected to.
  4. Run the CAS Gateway AutoUpdate tool.
  5. Click Find to discover the CAS Gateway on your network.
    1. Select the device from the list of discovered devices and click OK.
  6. Click Browse and select the new firmware file you want to send to the CAS Gateway.

    CAS Gateway AutoUpdate tool showing firmware browse/upload step

    • The firmware file should end with _APP.s19.
    • The firmware file should be at least 2 MB in file size (often closer to 3–5 MB).
    • The firmware file should come from CAS. Do not upload any other firmware files with this tool unless explicitly told to by Chipkin Automation Systems support.
  7. Check the Reboot when complete checkbox.
  8. Click Update.
    • The update may take a few minutes to complete.
    • You will be presented with a confirmation dialog upon completion.

Network Notes

The AutoUpdate tool uses UDP port 20034. If discovery or updating does not work as expected, confirm that your PC and the CAS Gateway are on the same network and that UDP port 20034 is permitted on your network path (for example, firewall rules).

If you have any problems, please contact Chipkin Automation Support for assistance.

FAQ: CAS Gateway Firmware Updates

What tool do I use to upgrade firmware on a CAS Gateway?
Use the CAS Gateway AutoUpdate tool provided by Chipkin/CAS.

Do my PC and the CAS Gateway need to be on the same network?
Yes. The instructions assume your PC is connected to the same network as the CAS Gateway so the tool can discover the device and send the firmware file.

What firmware file format is expected?
The firmware file should end with _APP.s19.

How long does the update take?
The update may take a few minutes, and you should expect a confirmation dialog when the process completes.

What network port does the AutoUpdate tool use?
The AutoUpdate tool uses UDP port 20034.

Can I upload any firmware file I find?
No. Use only firmware provided by CAS/Chipkin for your device. Do not upload other firmware files unless explicitly instructed by Chipkin Automation Systems support.

Contact Us

Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

*Required Field
*Required Field
I'd like to receive the newsletter. *Check email for confirmation.
*Required Field
8:00am - 12:00pm 12:00pm - 5:00pm
Message Sent Successfully