Azure Gateway - (BACnet IP, Modbus, Veeder-Root TLS, IOT, 1-Wire etc.)

Chipkin™ Azure Gateway is a protocol converter that can read data using various protocols and send the values to Microsoft’s Azure.
The BACnet IP Driver allows the Gateway to transfer data to and from devices over Ethernet UDP/IP using the BACnet IP protocol.
The Modbus RTU driver allows the Gateway to transfer data to and from devices via a serial RS485 connection using the Modbus protocol.
The Modbus TCP driver allows the Gateway to transfer data to and from devices over Ethernet TCP/IP using the Modbus protocol.
Chipkin's 1-Wire™ Gateway is a protocol converter for 1-Wire DS18b20 temperature sensors.
The Web (HTTP, XML, REST, Json, MQTT) driver allows the Gateway to push data to the Web via a variety of Protocols.
The Veeder-Root driver allows the Gateway to read data from a Veeder-Root Panel using the TLS350 protocol over RS232.
SKU:
CAS2700-73
CAS gateway 800 BLACK no Background -

Chipkin™ Azure Gateway is a protocol converter that can read data using various protocols and send the values to Microsoft’s Azure. The gateway operates by reading the values from downstream devices using their specific protocol and then stores them in an internal database.  The values are then sent to a Microsoft Azure system.

The gateway requires minimal configuration and can be considered a ‘plug and play’ component of any network system. It’s ready to operate ‘out of the box’ and can be installed without an engineer’s approval.  

CAS Hardware 700

The CAS 700 Hardware device contains 2x 9-pin serial ports (1x RS485 and 1xRS232), and one Ethernet port. The device also contains a microSD card where system files, assets, configurations, and logs are stored.

The device has the following system drivers that can be enabled:

  • HTTP REST Server - a passive web server with an API that users can interact with the device to get or set values
  • HTTP Push Driver - a driver that can be configured to push data in a specific format (JSON, XML, CSV) to a 3rd party web server. Current data formats are Chipkin's default JSON payload and VeederRoot Tank data as JSON. Please contact Chipkin for information on adding additional formats.

BACnet IP Driver

The CAS BACnet IP driver allows the CAS Gateway to transfer data to and from devices over Ethernet UDP/IP using the BACnet IP protocol.  The CAS Gateway can either be a Client, reading and storing values from a BACnet device, or a Server, making data available as BACnet objects.

The CAS BACnet IP Driver supports the following BACnet Services:

- Who-Is- Who-Has
- Read Property- Read Property Multiple
- Write Property- Write Property Multiple
- Subscribe COV     - Time Synchronization

Note: Chipkin is always updating the BACnet IP Driver. For a recent list of supported services, please visit www.chipkin.com or contact us. If there are services that you require that are not listed, please contact us to discuss how we can add them to the driver.

Modbus RTU Driver

The CAS Modbus RTU driver allows the CAS Gateway to transfer data to and from devices via a serial RS485 connection using the Modbus protocol.  The CAS Gateway can either be a Client, reading and controlling values from a slave, or a Server, serving data to a Modbus Master.

The CAS Modbus RTU Driver supports the following Modbus Functions:

- 01 (0x01) Read Coils- 05 (0x05) Write Single Coil
- 02 (0x02) Read Discrete Inputs- 06 (0x06) Write Single Register
- 03 (0x03) Read Holding Registers- 15 (0x0F) Write Multiple Coils
- 04 (0x04) Read Input Registers- 16 (0x10) Write Multiple Registers

Modbus TCP Driver

The CAS Modbus TCP driver allows the CAS Gateway to transfer data to and from devices over Ethernet TCP/IP using the Modbus protocol.  The CAS Gateway can either be a Client, reading and controlling values from a slave, or a Server, serving data to a Modbus Master.

The CAS Modbus TCP Driver supports the following Modbus Functions:

- 01 (0x01) Read Coils - 05 (0x05) Write Single Coil
- 02 (0x02) Read Discrete Inputs- 06 (0x06) Write Single Register
- 03 (0x03) Read Holding Registers    - 15 (0x0F) Write Multiple Coils
- 04 (0x04) Read Input Registers- 16 (0x10) Write Multiple Registers

1-Wire Driver

1-Wire™ Modbus® RTU/TCP, BACnet® and HTTP gateway is a protocol converter for 1-Wire DS18b20 temperature sensors. The gateway operates by reading the temperature data from the 1 or more DS18b20 1-wire sensors into an internal database. The values read from these sensors can then be read from Modbus® RTU/TCP, BACnet® and HTTP.

Web (HTTP, XML, REST, Json, MQTT) Driver

The Web Diver allows for data to be monitored by remote systems running applications that can issue HTTP or SOAP/XML GET requests – such applications can be easily developed by end users. Of course, this data is available using an Internet Browser such as Internet Explorer or Google Chrome

Veeder-Root Driver

The CAS Veeder-Root driver allows the CAS Gateway to read data from a Veeder-Root Panel using the TLS350 protocol over RS232. The CAS Gateway can connect to Veeder-Root TLS 300/350/450/4 series panels to read and store Tank and Sensor data. This driver only supports read-only functions and cannot command or configure the Veeder-Root panel. The Veeder-Root panel must have a valid RS232 comm card installed.

The CAS Veeder-Root driver supports the following TLS350 functions:

  • 101 - System Status Report
  • 201 - Tank Inventory Report
  • 202 - Tank Delivery Report
  • 406 - Relay Status Report
  • B38 - Vacuum Sensor Diagnostic Report

I'd like to inquire about the Azure Gateway - (BACnet IP, Modbus, Veeder-Root TLS, IOT, 1-Wire etc.) CAS2700-73. Please provide me with a quote for this product.

Specifications

CAS Hardware 700

The following specifications are common to all Chipkin gateways.

  • Certifications: UL and ULc approved
  • Ports:
    • 10/100BASE-T with RJ-45 connector
    • 1x RS232 port
    • 1x RS485 port (different models have additional ports)
  • Power: 7 - 24 VDC through an external power supply. (12V @ 90mA)
  • Operating temperature: 0 - 70 °C (32 - 158 °F)
  • LEDs: link, speed/data, power

Dimensions
  • Dimensions (LxWxH): 107 x 83 x 25 mm (4.2 x 3.25 x 1 in.)
  • Connection type: RS485 (jumper change to RS232)

Top


Bottom


Block Diagrams

/2017/mar/10-12-59-14_CAS2700-26 1-Wire Connection Diagram.jpg/2017/mar/10-16-51-56_CAS2700-02 Veeder Gateway Connection Diagram.jpg

Resources

All CAS 2500, 2700, 2800 products

A quick start guide with instructions for some of the basic operations of the CAS Gateway product line. Includes instructions for the following:

  • Detecting the CAS Gateway via the computer and settings its IP Address
  • Downloading the Firmware to the CAS Gateway
  • Downloading the Assets to the CAS Gateway
  • Downloading the Configuration to the CAS Gateway

Veeder-Root

The default configuration for a CAS 2700-02B Veeder-Root Gateway. 

Additional Information

CAS 2500/2700 RS485 Connector




Image result for rs485 2 wire to 4 wire


CAS Veeder Root Serial Connectors


CAS Veeder Root Quick Assembly Cable


Contact Us

Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

*Required Field
*Required Field
I'd like to receive the newsletter. *Check email for confirmation.
*Required Field
8:00am - 12:00pm 12:00pm - 5:00pm