Fike Cheetah to BACnet IP QuickServer Gateway

A FieldServer protocol Gateway that provides data exchange between Fike Cheetah to BACnet IP.
Our QuickServers are high performance, fully configurable, cost effective Building and Industrial Automation gateways to easily interface devices to networks in commercial buildings and industrial plants.
Every QuickServer includes browser-based tools for quick set-up and to perform diagnostics including determination of status, network settings, node information, map descriptors and more.
The premium QuickServer FS-QS-3X10 series comes equipped with dual Ethernet ports, RS485 and RS232 serial ports and is available with up to 10k point capacity.
The BACnet/IP driver allows the FieldServer to transfer data to and from devices over Ethernet using BACnet/IP protocol.
The Cheetah Protocol driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using the Cheetah device protocols (Legacy Cheetah Classic, Cheetah Xi and Cheetah MIM).
SKU:
FS-QS-3010-0387 (250 points),FS-QS-3110-0387 (500 points),FS-QS-3210-0387 (1000 points),FS-QS-3310-0387 (3000 points),FS-QS-3410-0387 (5000 points),FS-QS-3510-0387 (10000 points);
FS-QS-2010-0387 (250 points),FS-QS-2110-0387 (1000 points),FS-QS-2210-0387 (500 points),FS-QS-2310-0387 (3000 points),FS-QS-2410-0387 (5000 points);
FS-QS-1010-0387 (250 points),FS-QS-1210-0387 (500 points),FS-QS-1310-0387 (3000 points),FS-QS-1410-0387 (5000 points);
QuickServer Classic - QuickServer Classic


BACnet IP

The BACnet/IP driver allows the FieldServer to transfer data to and from devices over Ethernet using BACnet/IP protocol. The FieldServer can emulate either a Server or Client.

All information in a BACnet system is represented in terms of objects. The Object_Identifier is a 32-bit code that identifies the type of Object (also identified by the Object_Type Property) and its "Instance" number, which together uniquely identify the Object within its BACnet device. Theoretically, a BACnet device could have over four million Objects of a particular type. The Object_Name is a text string, which has a unique capability.

BACnet devices may broadcast queries for devices that contain Objects with a specific Object_Name. This can greatly simplify project setup.

BACnet requires one Device Object to be present in every BACnet device. The Device Object makes information about the device and its capabilities available to other devices on the networks. Before one BACnet device starts control-related communications with another, it needs to obtain some of the information presented by the other device's Device Object. Unlike other Objects, the Device Object's Instance number must be unique across the entire BACnet internetwork because it is used to uniquely identify the BACnet devices. It may be used to conveniently identify the BACnet device from other devices during installation.

Standard object types are used to hold real time data and other information. Each Object Type is referenced by a number, for example 0 represents an Analog Input. See Appendix D.1 for abbreviation list.

Each Object consists of a number of prescribed properties, the main property being the Present_Value. Objects are monitored and controlled through their properties.

The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

Classic QuickServer Gateway (Serial-Ethernet)

QuickServer is a high performance, fully configurable, cost-effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators worldwide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost-effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

QuickServer (Serial-Ethernet) is available in two series:

The FS-QS-1X10 Series is preloaded with two BAS drivers (two RS485 serial ports and one Ethernet port) Drivers from a list of over 150 protocols. There is a basic QuickServer that can handle up to 250 points and an enhanced QuickServer that can handle 500 points.

The FS-QS-1220 Series is preloaded with two BAS drivers (one RS485 serial port, one RS232 serial port, and one Ethernet port) Drivers from a list of over 150 protocols. Each QuickServer can handle up to 500 points.

Each QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

Quickserver Gateway (Serial-Ethernet)

The QuickServer is a high performance, fully configurable, cost effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators world-wide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

QuickServer (Serial-Ethernet) is available in two series:

The QuickServer FS-QS-2X10 series is available at four different point capacities. Each QuickServer is preloaded with two drivers (serial and/or Ethernet) from a customer’s choice of 140 different drivers, E.G. Modbus, BACnet, SNMP, EtherNet/IP and many more.

The FS-QS-2010 with 2 RS485 and 1 ethernet port can support up to 250 points. The FS-QS-2210 can support up to 500 points. The FS-QS-2310 can support up to 3,000 points. The FS-QS-2410 can support up to 5,000 points.

Equivalently the FS-QS-2020 with 1 RS485, 1 RS232 and 1 ethernet port can support up to 250 points. The FS-QS-2220 can support up to 500 points. The FS-QS-2320 can support up to 3,000 points. The FS-QS-2420 can support up to 5,000 points.

Every QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

Dual Ethernet Port Quickserver Gateway (Serial-Ethernet)

The QuickServer is a high performance, fully configurable, cost effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators world-wide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

The QuickServer FS-QS-3X10-F series is available at four different point capacities. Each QuickServer is preloaded with 140 different drivers, such as Modbus, BACnet, SNMP, EtherNet/IP and many more. See page 3 for the complete list. The FS-QS-3010-F can support up to 250 points. The FS-QS-3110-F can support up to 500 points. The FS-QS-3210-F can support up to 1,000 points. The FS-QS-3310-F can support up to 3,000 points. The FS-QS-3410-F can support up to 5,000 points. The FS-QS-3510-Fire can support up to 10,000 points.

With two Ethernet ports, the QuickServer allows data to move seamlessly across disparate subnets, using a dedicated port for Cloud connectivity. This port isolation allows for enhanced LAN security from the BMS/WAN/Cloud. An embedded OpenVPN Server enables secure remote access to Ethernet devices in the field.

Every QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

Fike Cheetah

The Cheetah Protocol driver allows the FieldServer to transfer data to and from devices over either RS- 232 or RS-485 using the Cheetah device protocols (Legacy Cheetah Classic, Cheetah Xi and Cheetah MIM). The driver supports messages sent from the Cybercat panel. Specifically, the driver supports message 1.02 which reports panel, zone and device states. The FieldServer can emulate either a Server or Client but it should be noted that it can only process unsolicited messages from the Cheetah devices. Thus, it does not provide an active Client driver. It is best to consider this driver as a consumer only driver with the data being produced by a Cheetah controller.

I'd like to inquire about the Fike Cheetah to BACnet IP QuickServer Gateway FS-QS-XXX0-0387. Please provide me with a quote for this product.

Specifications

Classic QuickServer Gateway (Serial-Ethernet)

Classic QuickServer Specs: FS-QS-1XX0

Depending on what hardware you require, the specifications will contain different options. For Example, M-bus section is only available on the FS-QS-1x50/FS-QS-1x51 devices where x is A for 16 devices, B for 32 devices and C for 64 devices. See images below for Port Support and product code check.



Environment
  • Operating Temperature: -40 to 75oC (-40 to 167oF)
  • Relative Humidity: 5-90% RH non-condensing
Power Requirements

9-30V DC or 12-24V AC, RS-422 = 15-30V DC or 12-24V AC, M-Bus = 12-24V DC (Slave: 550 mA, Master (1 Slave): 580 mA, Master (64 Slave):980 mA); 240 mA

Physical Dimensions
  • Dimensions (WxDxH): 4.5x2.9x1.6 in (11.5x7.4x4.1cm)
  • Weight: 0.4 lbs (0.2 Kg)
Other
  • Configuration/Diagnostic utilities
  • Capacity, max points: 250 for QS-10XX, 500 for QS-12XX, 3000 for QS-13XX, 5000 for QS-14XX
  • Table, Wall or DIN rail mount
Communication
  • Baud: 4800, 9600, 19200, 38400, 57600, 115200
  • Start Bit: 7, 8; Stop Bit: 1, 2
  • Parity: Even, Odd, None
LonMark Certification (FS-QS-1XX1)
  • SPID: 80:00:95:46:00:84:04:01
  • Profiles: 0000 - Node object, 0001 - Open Loop Sensor Object, 0003 - Open Loop Actuator Object
  • Ethernet: 1, 2
  • Parity: 10/100 BaseT
Approvals
  • TUV Approved: to UL 916, EN 60950-1, EN 50491-3 and CSA C22.2 standards
  • BTL Mark, RoHS Compliant, GOST-R Certified, CE and FCC
  • LonMark Certified: (FS-QS-1011/FS-QS-12X1)
Quickserver Gateway (Serial-Ethernet)

QuickServer Specs: FS-QS-2XX0


Environment
  • Operating Temperature: -20 to 70°C (-4 to 158oF)
  • Relative Humidity: 10-95% RH non-condensing
Power Requirements
  • Intput: 24VAC 0.125A, 12-24VDC 0.25A @12 VDC
  • Max Power: 3W


Physical Dimensions
  • Dimensions (WxDxH): 4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8cm)
  • Weight: 0.4 lbs (0.2 Kg)
Other

Web configuration
On-board diagnostics
DIN rail mount included

  • Capacity: 250 points FS-QS-20XX, 500 points FS-QS-22XX, 3000 points FS-QS-23XX, 5000 points FS-QS-24XX
Communication

FS-QS-2XX0

  • Baud: 9600, 19200, 34800, 57600, 76800
  • Serial (Galvanic Isolation) Ports: 1 x RS485, 1 x RS232/RS485
  • Ethernet Port: 10/100baseT, MDIX, DHCP

Approvals
  • UL 60950
  • IC Canada
  • RoHS Compliant
  • WEEE compliant
  • RoHS compliant
  • CE and FCC class B and C part 15

Dual Ethernet Port Quickserver Gateway (Serial-Ethernet)

Dual Ethernet Port QuickServers: FS-QS-3XX0

Environment
  • Operating Temperature: -20 to 70°C (-4 to 158°F)
  • Relative Humidity: 10-95% RH non-condensing
Power Requirements
  • Input: 24VAC 0.125A, 9-30VDC 0.25A @12 VDC
  • Max Power: 3W
Physical Dimensions
  • Dimensions (WxDxH): 4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8cm)
  • Weight: 0.4 lbs (0.2 Kg)
Other

Web configuration
On-board diagnostics
DIN rail mount included

Communication

FS-QS-3XX0

  • Baud: 9600, 19200, 38400, 57600, 76800, 115000
  • Serial (Galvanic Isolation): 1 x RS-485/RS-232 & 1 x RS-485
  • Ethernet: 2 x 10/100BaseT, MDIX, DHCP
Approvals
  • CE and FCC Class B & C Part 15
  • BTL Marked
  • UL 60950-1 and CAN/CSA C22 2
  • IC Canada & KC Certification
  • RoHS3 and WEEE complaint

Block Diagrams

imports/blockDiagrams/LP Fike Cheetah.jpg

Contact Us

Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

*Required Field
*Required Field
I'd like to receive the newsletter. *Check email for confirmation.
*Required Field
8:00am - 12:00pm 12:00pm - 5:00pm