CALL NOW CALL NOW CALL NOW GATEWAY SELECTOR CALL NOW GATEWAY SELECTOR LEARN MORE LEARN MORE PROCEED TO CHECK-OUT SUBSCRIBE TO OUR RSS FEED SEARCH GATEWAYS NOW SEND MESSAGE SUBMIT

GE-SNP to BACnet IP QuickServer Gateway

A FieldServer protocol gateway that provides data exchange between GE-SNP and BACnet IP.
QuickServer is a high performance, fully configurable, cost effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.
The GE-SNP Serial driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using GE-SNP Serial protocol.
The BACnet/IP driver allows the FieldServer to transfer data to and from devices over Ethernet using BACnet/IP protocol.
SKU:
FS-QS-1XX0-0274
Max Points: 250, 500
25-11-39-56_Quickserver Gateways (serial-Ethernet).png - /2018/jan/25-11-39-56_Quickserver Gateways (serial-Ethernet).png

Quickserver Gateway (Serial-Ethernet)

QuickServer is a high performance, fully configurable, cost-effective Building and Industrial Automation gateway for integrators to easily interface devices to networks in commercial buildings and industrial plants.

System integrators worldwide have benefitted from the value of the powerful line of interoperability gateways offered by FieldServer. Now, QuickServer adds to that value by running the same robust FieldServer protocol conversion software on a highly cost-effective platform backed by the experience, engineering expertise and proven technical support that integrators have come to expect from FieldServer.

QuickServer (Serial-Ethernet) is available in two series:

The FS-QS-1X10 Series is preloaded with two BAS drivers (two RS485 serial ports and one Ethernet port) Drivers from a list of over 150 protocols. There is a basic QuickServer that can handle up to 250 points and an enhanced QuickServer that can handle 500 points.

The FS-QS-1220 Series is preloaded with two BAS drivers (one RS485 serial port, one RS232 serial port, and one Ethernet port) Drivers from a list of over 150 protocols. Each QuickServer can handle up to 500 points.

Each QuickServer includes browser-based tools to make it easy to set-up QuickServer and perform diagnostics including determination of status, network settings, node information, map descriptors and more. The USB flash drive also includes the Discovery utility to determine what FieldServers are on a network.

BACnet IP

The BACnet/IP driver allows the FieldServer to transfer data to and from devices over Ethernet using BACnet/IP protocol. The FieldServer can emulate either a Server or Client.

All information in a BACnet system is represented in terms of objects. The Object_Identifier is a 32-bit code that identifies the type of Object (also identified by the Object_Type Property) and its "Instance" number, which together uniquely identify the Object within its BACnet device. Theoretically, a BACnet device could have over four million Objects of a particular type. The Object_Name is a text string, which has a unique capability.

BACnet devices may broadcast queries for devices that contain Objects with a specific Object_Name. This can greatly simplify project setup.

BACnet requires one Device Object to be present in every BACnet device. The Device Object makes information about the device and its capabilities available to other devices on the networks. Before one BACnet device starts control-related communications with another, it needs to obtain some of the information presented by the other device's Device Object. Unlike other Objects, the Device Object's Instance number must be unique across the entire BACnet internetwork because it is used to uniquely identify the BACnet devices. It may be used to conveniently identify the BACnet device from other devices during installation.

Standard object types are used to hold real time data and other information. Each Object Type is referenced by a number, for example 0 represents an Analog Input. See Appendix D.1 for abbreviation list.

Each Object consists of a number of prescribed properties, the main property being the Present_Value. Objects are monitored and controlled through their properties.

The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.

GE-SNP

The GE-SNP Serial driver allows the FieldServer to transfer data to and from devices over either RS-232 or RS-485 using GE-SNP Serial protocol.

The FieldServer can emulate either a Server or Client.

The FieldServer provides functions to read and write PLC memory and change the privilege level. Standard SNP mailbox messages are used.

The driver does not support Datagram messages and cannot parse them. These messages are defined by the SNP protocol to allow multiple data types to be packed into one message. They are not commonly used by the HMI and 3rd party applications and are inconsistent with the FieldServer’s Write Through and Port Expander capabilities.

The driver can expose communications statistics in a Data Array so that downstream devices can monitor them

Specifications

Quickserver Gateway (Serial-Ethernet)

Environment
  • Operating Temperature: -40 to 75℃ (-40 to 167°F)
  • Relative Humidity: 5-90% RH non-condensing
Power Requirements

9-30V DC or 12-24V AC
(RS-422 = 15-30V DC or 12-24V AC)
(M-Bus = 12-24V DC)
Current draw: @ 12V

  • FS-QS-1010, FS-QS-1210, FS-QS-1220: 240 mA

M-Bus:

  • Slave: 550 mA @ 12V
  • Master (1 Slave): 580 mA @ 12V
  • Master (64 Slave): 980 mA @ 12V
Physical Dimensions
  • Dimensions (WxDxH): 4.5x2.9x1.6 in. (11.5x7.4x4.1cm
  • Weight: 0.4 lbs (0.2 Kg)
  • Input voltage: 24 V DC nominal: 10-30V DC
Other

Configuration/Diagnostic utilities

  • Capacity: 250 points FS-QS-11XX. (500 points FS-QS-12XX)
  • Table, Wall or DIN rail mount
Communication
  • Baud: 4800, 9600, 19200, 38400, 57600, 115200
  • Start Bit: 7, 8
  • Stop Bit: 1, 2
  • Parity: Even, Odd, None
LonMark Certification on the QuickServer FS-QS-1XX1-XXX
  • SPID: 80:00:95:46:00:84:04:01
  • Profiles: 0000 - Node object (1), 0001 - Open Loop Sensor Object (5), 0003 - Open Loop Actuator Object (5)
  • Ethernet: 1, 2
  • Parity: 10/100 BaseT
Approvals
  • TUV Approved: to UL 916, EN 60950-1, EN 50491-3 and CSA C22.2 standards
  • BTL Mark:
  • LonMark Certified: (FS-QS-1011 and FS-QS-12X1)
  • RoHS Compliant
  • GOST-R Certified
  • CE and FCC

Dimensions

Block Diagrams

imports/blockDiagrams/LP GE Fanuc EGD SRTP SNP SNPx.jpg

Gateway Selector

Select your combination of protocols.
Protocol 1
Protocol 2

Related Products

Contact Us

Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

*Required Field
I'd like to receive the newsletter. *Check email for confirmation.
*Required Field
Preferred Time To Be Contacted (PST)
8:00am - 12:00pm 12:00pm - 5:00pm