Differential Pressure Flowmeters

Differential pressure flowmeters are also known as Head type flowmeters. They are the most prevalent type of flowmeters in use today. It has been projected that more than 50 percent of all liquid flow measurement applications make use of this type of unit. The basic Working principle of differential pressure flowmeters is based upon the Bernoullis Equation which states the fact that the pressure drop across the meter is directly proportional to the square of the flow rate. The flow rate is calculated by measuring the pressure differential and extracting its square root.

Basic Elements

Just like other flowmeters, differential pressure flowmeters consist of two elements. They are: A primary element: This element causes a change in kinetic energy which results in the differential pressure in the pipe. The unit must be suitably matched to the

  • pipe size
  • flow conditions and
  • the liquid's properties

Besides, the measurement accuracy of the element must be fine over a practical range. A secondary element:The secondary element measures the differential pressure created by primary element and gives the signal or read-out which is in turn transformed to the actual flow value.

Types of Differential Pressure Flowmeters

Most widely used differential pressure flowmeters are:

  • Orifice Plates
  • Flow Nozzles
  • Venturi Tubes
  • Variable Area flowmeters, i.e. Rotameters

Accuracy & Rangeability

Performance of a head-type flowmeter installation is a function of the

  • precision of the flow element and
  • the accuracy of the d/p cell

On average, flow element precision is expressed in percentage of actual reading terms, whereas d/p cell accuracy is stated as a percentage of calibrated span. A d/p cell typically provides accuracy of ±0.2% of the calibrated span. With no detrimental effect on accuracy, rangeability of a flowmeter can be extra enhanced by employing several d/p flowmeters in parallel runs.

Errors and Noise

In case of compressible fluids, the ratio of differential pressure divided by upstream pressure should not exceed 0.25 for reduction of error and correction of density. Metering errors caused due to wrong installation of the primary element can become considerable i.e. up to 10%. Following are the possible causes of these errors:

  • the condition of the mating pipe sections
  • insufficient straight pipe runs
  • pressure tap and lead line design errors
  • In turbulent flow conditions, not more than 10% of the d/p signal could possibly be noise produced by disturbances from valves and fittings. These disturbances can be both up- and downstream of the element, and by the element itself. To sort out this noise, a damping is provided in d/p cells which prove to be adequate for majority of the applications. Rigorous noise can be diminished by applying two or more pressure taps connected in parallel on both sides of the d/p cell.
  • Did you know that we also do Modbus Integration Solutions?

    Chipkin has Modbus solutions for almost every situation. We are experts in Modbus RTU/TCP communication and carry a wide variety of Modbus products:

    https://cdn.chipkin.com/assets/uploads/2021/Aug/QS-1XXOQS-2XX0QS-3XX0_02-15-06-56__60644.1627501719_05-16-06-49.png

    Sources

    • OmegaTech
    • Engineering Toolbox
    • Omega Literature

    Contact Us

    Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

    *Required Field
    *Required Field
    I'd like to receive the newsletter. *Check email for confirmation.
    *Required Field
    8:00am - 12:00pm 12:00pm - 5:00pm
    Message Sent Successfully