Lonworks - Can you show me an example of typical FieldServer / QuickServer Veeder Lonworks points

DO NOT USE THIS DATA – IT IS SUBJECT TO CHANGE AND IS PROVIDED FOR REFERENCE ONLY.The points listed and the Lonworks addresses allocated are typical. We strongly advise you not to hand this to the contractor implementing theLonworks Client. They should use the actual map provided for your project.


//!!!Ignore SNVT_Index = Data will change
Map_Descriptors
Map_Descriptor_Name  Data_Array_Name Data_Array_Offset Node_Name Function Lon_Function SNVT_Index SNVT_Type SNVT_Option
nviAlarmReset  VEED_DA_RESET 0 Virtual_Veeder Server NVUI 1 SNVT_switch state
nviStartLeakTst  VEED_DA_START 0 Virtual_Veeder Server NVUI 2 SNVT_switch state
nviStopLeakTest  VEED_DA_STOP 0 Virtual_Veeder Server NVUI 3 SNVT_switch state
  
//Inventory Data - Sample of points for Tank 3 and 4
Map_Descriptors
Map_Descriptor_Name  Data_Array_Name Data_Array_Offset Node_Name Function Lon_Function SNVT_Index SNVT_Type SNVT_Option
nvoT3_ProdCode  VEED_DA_INVENT3 0 Virtual_Veeder wrbx NVUOIMX 301 SNVT_count_f -
nvoT3_TankStatus  VEED_DA_INVENT3 1 Virtual_Veeder wrbx NVUOIMX 302 SNVT_count_f -
nvoT3_Volume  VEED_DA_INVENT3 2 Virtual_Veeder wrbx NVUOIMX 303 SNVT_vol_f -
nvoT3_TC_Volume  VEED_DA_INVENT3 3 Virtual_Veeder wrbx NVUOIMX 304 SNVT_vol_f -
nvoT3_Ullage  VEED_DA_INVENT3 4 Virtual_Veeder wrbx NVUOIMX 305 SNVT_length_mil -
nvoT3_Height  VEED_DA_INVENT3 5 Virtual_Veeder wrbx NVUOIMX 306 SNVT_length_mil -
nvoT3_Water  VEED_DA_INVENT3 6 Virtual_Veeder wrbx NVUOIMX 307 SNVT_length_mil -
nvoT3_Temp  VEED_DA_INVENT3 7 Virtual_Veeder wrbx NVUOIMX 308 SNVT_temp_f -
nvoT3_WaterVol  VEED_DA_INVENT3 8 Virtual_Veeder wrbx NVUOIMX 309 SNVT_vol_f -
nvoT4_ProdCode  VEED_DA_INVENT4 0 Virtual_Veeder wrbx NVUOIMX 401 SNVT_count_f -
nvoT4_TankStat  VEED_DA_INVENT4 1 Virtual_Veeder wrbx NVUOIMX 402 SNVT_count_f -
nvoT4_Volume  VEED_DA_INVENT4 2 Virtual_Veeder wrbx NVUOIMX 403 SNVT_vol_f -
nvoT4_TC_Volume  VEED_DA_INVENT4 3 Virtual_Veeder wrbx NVUOIMX 404 SNVT_Index -
nvoT4_Ullage  VEED_DA_INVENT4 4 Virtual_Veeder wrbx NVUOIMX 405 SNVT_length_mil -
nvoT4_Height  VEED_DA_INVENT4 5 Virtual_Veeder wrbx NVUOIMX 406 SNVT_length_mil -
nvoT4_Water  VEED_DA_INVENT4 6 Virtual_Veeder wrbx NVUOIMX 407 SNVT_length_mil -
nvoT4_Temp  VEED_DA_INVENT4 7 Virtual_Veeder wrbx NVUOIMX 408 SNVT_temp_f -
nvoT4_WaterVol  VEED_DA_INVENT4 8 Virtual_Veeder wrbx NVUOIMX 409 SNVT_vol_f -

//Vacuum Sensor SNVT's - Sample of points for vacuum sensor #1
nvoU1_SerialNum VEED_DA_VACUUM1 2 Virtual_Veeder wrbx NVUOIMX 1002 SNVT_count_f -
nvoU1_EvacState VEED_DA_VACUUM1 3 Virtual_Veeder wrbx NVUOIMX 1003 SNVT_count_f -
nvoU1_FluidStat VEED_DA_VACUUM1 4 Virtual_Veeder wrbx NVUOIMX 1004 SNVT_count_f -
nvoU1_CtrlVlv VEED_DA_VACUUM1 5 Virtual_Veeder wrbx NVUOIMX 1005 SNVT_count_f -
nvoU1_ValidLR VEED_DA_VACUUM1 6 Virtual_Veeder wrbx NVUOIMX 1007 SNVT_count_f -
nvoU1_LeakRatee VEED_DA_VACUUM1 8 Virtual_Veeder wrbx NVUOIMX 1008 SNVT_count_f -
nvoU1_LeakRatex VEED_DA_VACUUM1 9 Virtual_Veeder wrbx NVUOIMX 1009 SNVT_count_f -
nvoU1_ValidTime VEED_DA_VACUUM1 10 Virtual_Veeder wrbx NVUOIMX 1010 SNVT_count_f -
nvoU1_TimeNoVac VEED_DA_VACUUM1 12 Virtual_Veeder wrbx NVUOIMX 1002 SNVT_count_f -
nvoU1_ValidER VEED_DA_VACUUM1 13 Virtual_Veeder wrbx NVUOIMX 1003 SNVT_count_f -
nvoU1_EvacRatio VEED_DA_VACUUM1 15 Virtual_Veeder wrbx NVUOIMX 1015 SNVT_count_f -
nvoU1_EvacRatiox VEED_DA_VACUUM1 16 Virtual_Veeder wrbx NVUOIMX 1016 SNVT_count_f -
nvoU1_ER_Press VEED_DA_VACUUM1 17 Virtual_Veeder wrbx NVUOIMX 1017 SNVT_count_f -
nvoU1_ER_pressx VEED_DA_VACUUM1 18 Virtual_Veeder wrbx NVUOIMX 1018 SNVT_count_f -
nvoU1_FaultBits VEED_DA_VACUUM1 19 Virtual_Veeder wrbx NVUOIMX 1019 SNVT_count_f -
nvoU1_NumValues VEED_DA_VACUUM1 20 Virtual_Veeder wrbx NVUOIMX 1020 SNVT_count_f -
nvoU1_CompnstdP VEED_DA_VACUUM1 21 Virtual_Veeder wrbx NVUOIMX 1021 SNVT_count_f -
nvoU1_CompnstdPx VEED_DA_VACUUM1 22 Virtual_Veeder wrbx NVUOIMX 1022 SNVT_count_f -
nvoU1_UncompP VEED_DA_VACUUM1 23 Virtual_Veeder wrbx NVUOIMX 1023 SNVT_count_f -
nvoU1_UncompPx VEED_DA_VACUUM1 24 Virtual_Veeder wrbx NVUOIMX 1024 SNVT_count_f -
  
//System Alarms - present in all systems
nvoSys_Normal VEED_DA_101 0 Virtual_Veeder wrbx NVUOIMX 10000 SNVT_switch state
nvoSys_SysAlm VEED_DA_S1 1 Virtual_Veeder wrbx NVUOIMX 10001 SNVT_switch state
nvoSys_TankAlm VEED_DA_S1 2 Virtual_Veeder wrbx NVUOIMX 10002 SNVT_switch state
nvoSys_LiqSens VEED_DA_S1 3 Virtual_Veeder wrbx NVUOIMX 10003 SNVT_switch state
nvoSys_VapSens VEED_DA_S1 4 Virtual_Veeder wrbx NVUOIMX 10004 SNVT_switch state
nvoSys_InputAlm VEED_DA_S1 5 Virtual_Veeder wrbx NVUOIMX 10005 SNVT_switch state
nvoSys_VolLine VEED_DA_S1 6 Virtual_Veeder wrbx NVUOIMX 10006 SNVT_switch state
nvoSys_Gwater VEED_DA_S1 7 Virtual_Veeder wrbx NVUOIMX 10007 SNVT_switch state
nvoSys_Typea VEED_DA_S1 8 Virtual_Veeder wrbx NVUOIMX 10008 SNVT_switch state
nvoSys_Typeb VEED_DA_S1 12 Virtual_Veeder wrbx NVUOIMX 10001 SNVT_switch state
nvoSys_Universal VEED_DA_S1 13 Virtual_Veeder wrbx NVUOIMX 10013 SNVT_switch state
nvoSys_AutoDial VEED_DA_S1 14 Virtual_Veeder wrbx NVUOIMX 10014 SNVT_switch state
nvoSys_MechDisp VEED_DA_S1 18 Virtual_Veeder wrbx NVUOIMX 10018 SNVT_switch state
nvoSys_ElecDisp VEED_DA_S1 19 Virtual_Veeder wrbx NVUOIMX 10019 SNVT_switch state
nvoSys_ProdAlm VEED_DA_S1 20 Virtual_Veeder wrbx NVUOIMX 10020 SNVT_switch state
nvoSys_PressLeak VEED_DA_S1 21 Virtual_Veeder wrbx NVUOIMX 10021 SNVT_switch state
nvoSys_WPLLD VEED_DA_S1 26 Virtual_Veeder wrbx NVUOIMX 10026 SNVT_switch state
nvoSys_External VEED_DA_S1 99 Virtual_Veeder wrbx NVUOIMX 10099 SNVT_switch state
  
//Tank Alarms - Sample is points for Tank #3
nvoT3_AnyAlm  VEED_DA_T3 0 Virtual_Veeder wrbx NVUOIMX 203000 SNVT_switch state
nvoT3_SetupWarn  VEED_DA_T3 1 Virtual_Veeder wrbx NVUOIMX 203001 SNVT_switch state
nvoT3_LeakAlm  VEED_DA_T3 2 Virtual_Veeder wrbx NVUOIMX 203002 SNVT_switch state
nvoT3_HiWaterAlm  VEED_DA_T3 3 Virtual_Veeder wrbx NVUOIMX 203003 SNVT_switch state
nvoT3_Overfill  VEED_DA_T3 4 Virtual_Veeder wrbx NVUOIMX 203004 SNVT_switch state
nvoT3_LoProduct  VEED_DA_T3 5 Virtual_Veeder wrbx NVUOIMX 203005 SNVT_switch state
nvoT3_SuddenLos  VEED_DA_T3 6 Virtual_Veeder wrbx NVUOIMX 203006 SNVT_switch state
nvoT3_HiProduct  VEED_DA_T3 7 Virtual_Veeder wrbx NVUOIMX 203007 SNVT_switch state
nvoT3_InvalidFL  VEED_DA_T3 8 Virtual_Veeder wrbx NVUOIMX 203008 SNVT_switch state
nvoT3_ProbeOut  VEED_DA_T3 9 Virtual_Veeder wrbx NVUOIMX 203009 SNVT_switch state
nvoT3_HiWaterWrn  VEED_DA_T3 10 Virtual_Veeder wrbx NVUOIMX 203010 SNVT_switch state
nvoT3_DeliverWrn  VEED_DA_T3 11 Virtual_Veeder wrbx NVUOIMX 203011 SNVT_switch state
nvoT3_MaxProd  VEED_DA_T3 12 Virtual_Veeder wrbx NVUOIMX 203012 SNVT_switch state
nvoT3_GrossLeak  VEED_DA_T3 13 Virtual_Veeder wrbx NVUOIMX 203013 SNVT_switch state
nvoT3_PeriodLeak  VEED_DA_T3 14 Virtual_Veeder wrbx NVUOIMX 203014 SNVT_switch state
nvoT3_AnnualLeak  VEED_DA_T3 15 Virtual_Veeder wrbx NVUOIMX 203015 SNVT_switch state
nvoT3_PeriodWrn  VEED_DA_T3 16 Virtual_Veeder wrbx NVUOIMX 203016 SNVT_switch state
nvoT3_AnnualWrn  VEED_DA_T3 17 Virtual_Veeder wrbx NVUOIMX 203017 SNVT_switch state
nvoT3_PeriodAlm  VEED_DA_T3 18 Virtual_Veeder wrbx NVUOIMX 203018 SNVT_switch state
nvoT3_AnnualAlm  VEED_DA_T3 19 Virtual_Veeder wrbx NVUOIMX 203019 SNVT_switch state
nvoT3_LeakTest  VEED_DA_T3 20 Virtual_Veeder wrbx NVUOIMX 203020 SNVT_switch state
nvoT3_NoCSLD  VEED_DA_T3 21 Virtual_Veeder wrbx NVUOIMX 203021 SNVT_switch state
nvoT3_Siphon  VEED_DA_T3 22 Virtual_Veeder wrbx NVUOIMX 203022 SNVT_switch state
nvoT3_CSLDRate  VEED_DA_T3 23 Virtual_Veeder wrbx NVUOIMX 203023 SNVT_switch state
nvoT3_AccuChart  VEED_DA_T3 24 Virtual_Veeder wrbx NVUOIMX 203024 SNVT_switch state
nvoT3_HRMWarn  VEED_DA_T3 25 Virtual_Veeder wrbx NVUOIMX 203025 SNVT_switch state
nvoT3_HRMAlm  VEED_DA_T3 26 Virtual_Veeder wrbx NVUOIMX 203026 SNVT_switch state
nvoT3_ColdWarn  VEED_DA_T3 27 Virtual_Veeder wrbx NVUOIMX 203027 SNVT_switch state
nvoT3_Missing  VEED_DA_T3 28 Virtual_Veeder wrbx NVUOIMX 203028 SNVT_switch state
  
Liquid Sensor Alarms - Sample is for Lquid Sensor #1
nvoL1_AnyAlm  VEED_DA_L1 0 Virtual_Veeder wrbx NVUOIMX 401000 SNVT_switch state
nvoL1_SetupWarn VEED_DA_L1 2 Virtual_Veeder wrbx NVUOIMX 401002 SNVT_switch state
nvoL1_FuelAlm  VEED_DA_L1 3 Virtual_Veeder wrbx NVUOIMX 401003 SNVT_switch state
nvoL1_OutAlm  VEED_DA_L1 4 Virtual_Veeder wrbx NVUOIMX 401004 SNVT_switch state
nvoL1_ShortAlm  VEED_DA_L1 5 Virtual_Veeder wrbx NVUOIMX 401005 SNVT_switch state
nvoL1_WaterAlm  VEED_DA_L1 6 Virtual_Veeder wrbx NVUOIMX 401006 SNVT_switch state
nvoL1_WaterOut  VEED_DA_L1 7 Virtual_Veeder wrbx NVUOIMX 401007 SNVT_switch state
nvoL1_HiLiqAlm  VEED_DA_L1 8 Virtual_Veeder wrbx NVUOIMX 401008 SNVT_switch state
nvoL1_LoLiqAlm  VEED_DA_L1 9 Virtual_Veeder wrbx NVUOIMX 401009 SNVT_switch state
nvoL1_LiqWarn  VEED_DA_L1 10 Virtual_Veeder wrbx NVUOIMX 401010 SNVT_switch state
  
//Vapor Sensor Alarms - Sample is for Vapor Sensor #1
nvoV1_AnyAlm  VEED_DA_V1 0 Virtual_Veeder wrbx NVUOIMX 401000 SNVT_switch state
nvoV1_SetupWarn VEED_DA_V1 2 Virtual_Veeder wrbx NVUOIMX 401002 SNVT_switch state
nvoV1_FuelAlm  VEED_DA_V1 3 Virtual_Veeder wrbx NVUOIMX 401003 SNVT_switch state
nvoV1_OutAlm  VEED_DA_V1 4 Virtual_Veeder wrbx NVUOIMX 401004 SNVT_switch state
nvoV1_ShortAlm  VEED_DA_V1 5 Virtual_Veeder wrbx NVUOIMX 401005 SNVT_switch state
nvoV1_WaterAlm  VEED_DA_V1 6 Virtual_Veeder wrbx NVUOIMX 401006 SNVT_switch state
nvoV1_WaterOut  VEED_DA_V1 7 Virtual_Veeder wrbx NVUOIMX 401007 SNVT_switch state
nvoV1_HiLiqAlm  VEED_DA_V1 8 Virtual_Veeder wrbx NVUOIMX 401008 SNVT_switch state
nvoV1_LoLiqAlm  VEED_DA_V1 9 Virtual_Veeder wrbx NVUOIMX 401009 SNVT_switch state
nvoV1_LiqWarn  VEED_DA_V1 10 Virtual_Veeder wrbx NVUOIMX 401010 SNVT_switch state

XIF File

Download the file

File: fserver-25.xif generated by LonDriver Revision 1.26(a), XIF Version 4.0

Copyright (c) 2000-2005 by FieldServer Technologies

All Rights Reserved. Run on Wed Jul 28 06:58:51 2010

90:00:95:47:1E:02:04:F6

2 15 1 108 0 14 11 3 3 12 14 11 11 11 11 3 0 16 63 0 1 11 108

0 5 7 13 28 0 0 15 5 3 109 63

1 7 1 0 4 4 4 15 200 0

78125 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 1 5 8 5 12 14 15

*

"Veeder Demo Rev5

VAR nviAlarmReset 0 0 0 0

0 1 63 0 0 0 0 0 0 0 0 0 0

*

95 * 2

1 0 0 0 0

1 0 0 1 0

VAR nviStartLeakTst 1 0 0 0

0 1 63 0 0 0 0 0 0 0 0 0 0

*

95 * 2

1 0 0 0 0

1 0 0 1 0

VAR nviStopLeakTest 2 0 0 0

0 1 63 0 0 0 0 0 0 0 0 0 0

*

95 * 2

1 0 0 0 0

1 0 0 1 0

VAR nvoT3_ProdCode 3 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_TankStatus 4 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Volume 5 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_TC_Volume 6 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Ullage 7 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Height 8 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Water 9 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Temp 10 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_WaterVol 11 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_ProdCode 12 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_TankStat 13 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Volume 14 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_TC_Volume 15 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Ullage 16 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Height 17 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Water 18 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_Temp 19 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT4_WaterVol 20 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_SerialNum 21 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_EvacState 22 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_FluidStat 23 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_CtrlVlv 24 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ValidLR 25 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_LeakRatee 26 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_LeakRatex 27 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ValidTime 28 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_TimeNoVac 29 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ValidER 30 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_EvacRatio 31 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_EvacRatiox 32 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ER_Press 33 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_ER_pressx 34 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_FaultBits 35 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_NumValues 36 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_CompnstdP 37 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_CompnstdPx 38 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_UncompP 39 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoU1_UncompPx 40 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Normal 41 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_SysAlm 42 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_TankAlm 43 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_LiqSens 44 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_VapSens 45 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_InputAlm 46 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_VolLine 47 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Gwater 48 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Typea 49 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Typeb 50 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_Universal 51 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_AutoDial 52 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_MechDisp 53 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_ElecDisp 54 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_ProdAlm 55 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_PressLeak 56 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_WPLLD 57 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoSys_External 58 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnyAlm 59 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_SetupWarn 60 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_LeakAlm 61 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HiWaterAlm 62 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Overfill 63 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_LoProduct 64 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_SuddenLos 65 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HiProduct 66 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_InvalidFL 67 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_ProbeOut 68 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HiWaterWrn 69 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_DeliverWrn 70 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_MaxProd 71 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_GrossLeak 72 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_PeriodLeak 73 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnnualLeak 74 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_PeriodWrn 75 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnnualWrn 76 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_PeriodAlm 77 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AnnualAlm 78 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_LeakTest 79 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_NoCSLD 80 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Siphon 81 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_CSLDRate 82 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_AccuChart 83 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HRMWarn 84 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_HRMAlm 85 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_ColdWarn 86 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoT3_Missing 87 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_AnyAlm 88 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_SetupWarn 89 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_FuelAlm 90 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_OutAlm 91 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_ShortAlm 92 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_WaterAlm 93 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_WaterOut 94 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_HiLiqAlm 95 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_LoLiqAlm 96 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoL1_LiqWarn 97 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_AnyAlm 98 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_SetupWarn 99 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_FuelAlm 100 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_OutAlm 101 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_ShortAlm 102 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_WaterAlm 103 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_WaterOut 104 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_HiLiqAlm 105 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_LoLiqAlm 106 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

VAR nvoV1_LiqWarn 107 0 0 0

0 1 63 1 0 0 0 0 0 0 0 0 0

*

51 * 1

4 0 4 0 0

Contact Us

Contact us via phone (+1 866-383-1657) or leave a detailed message below for sales, support, or any other needs

*Required Field
*Required Field
I'd like to receive the newsletter. *Check email for confirmation.
*Required Field
8:00am - 12:00pm 12:00pm - 5:00pm
Message Sent Successfully