Multistack Compu25 - Can you show me a sample points list for a heat pump?

This points list may change when firmware is updated or the device is configured differently. Contact us to check for the latest points list.

Map_Descriptor_NameData_TypeAddressFunctionUnits
CAPACITYAv001SERVERNo_Units
DEMANDAv002SERVERNo_Units
NUMBER OF COMPSAv003SERVERNo_Units
CURRENT FAULTSAv004SERVERNo_Units
OPERATING MODEAv005SERVERNo_Units
ENT LOAD TEMPAv006SERVERNo_Units
LEV LOAD TEMPAv007SERVERNo_Units
ENT SOURCE TEMPAv008SERVERNo_Units
LEV SOURCE TEMPAv009SERVERNo_Units
COOL UPSETPTAv010SERVERNo_Units
COOL LOWSETPTAv011SERVERNo_Units
COOL VSPAv012SERVERNo_Units
COOL TDIFFAv013SERVERNo_Units
HEAT UPSETPTAv014SERVERNo_Units
HEAT LOWSETPTAv015SERVERNo_Units
HEAT VSPAv016SERVERNo_Units
HEAT TDIFFAv017SERVERNo_Units
LOAD LIMITAv018SERVERNo_Units
FAIL INDICATORAv019SERVERNo_Units
LEAD COMPRESSORAv020SERVERNo_Units
FLUSH TIMEAv021SERVERNo_Units
FLUSH DURATIONAv022SERVERNo_Units
MONTHAv023SERVERNo_Units
DAYAv024SERVERNo_Units
YEARAv025SERVERNo_Units
HOURAv026SERVERNo_Units
MINUTEAv027SERVERNo_Units
C1 SUCTION TEMPAv028SERVERNo_Units
C1 LLW TEMPAv029SERVERNo_Units
C1 LSW TEMPAv030SERVERNo_Units
C2 SUCTION TEMPAv031SERVERNo_Units
C2 LLW TEMPAv032SERVERNo_Units
C2 LSW TEMPAv033SERVERNo_Units
C3 SUCTION TEMPAv034SERVERNo_Units
C3 LLW TEMPAv035SERVERNo_Units
C3 LSW TEMPAv036SERVERNo_Units
C4 SUCTION TEMPAv037SERVERNo_Units
C4 LLW TEMPAv038SERVERNo_Units
C4 LSW TEMPAv039SERVERNo_Units
C5 SUCTION TEMPAv040SERVERNo_Units
C5 LLW TEMPAv041SERVERNo_Units
C5 LSW TEMPAv042SERVERNo_Units
C6 SUCTION TEMPAv043SERVERNo_Units
C6 LLW TEMPAv044SERVERNo_Units
C6 LSW TEMPAv045SERVERNo_Units
C7 SUCTION TEMPAv046SERVERNo_Units
C7 LLW TEMPAv047SERVERNo_Units
C7 LSW TEMPAv048SERVERNo_Units
C8 SUCTION TEMPAv049SERVERNo_Units
C8 LLW TEMPAv050SERVERNo_Units
C8 LSW TEMPAv051SERVERNo_Units
C9 SUCTION TEMPAv052SERVERNo_Units
C9 LLW TEMPAv053SERVERNo_Units
C9 LSW TEMPAv054SERVERNo_Units
C10 SUCTION TEMPAv055SERVERNo_Units
C10 LLW TEMPAv056SERVERNo_Units
C10 LSW TEMPAv057SERVERNo_Units
C11 SUCTION TEMPAv058SERVERNo_Units
C11 LLW TEMPAv059SERVERNo_Units
C11 LSW TEMPAv060SERVERNo_Units
C12 SUCTION TEMPAv061SERVERNo_Units
C12 LLW TEMPAv062SERVERNo_Units
C12 LSW TEMPAv063SERVERNo_Units
C13 SUCTION TEMPAv064SERVERNo_Units
C13 LLW TEMPAv065SERVERNo_Units
C13 LSW TEMPAv066SERVERNo_Units
C14 SUCTION TEMPAv067SERVERNo_Units
C14 LLW TEMPAv068SERVERNo_Units
C14 LSW TEMPAv069SERVERNo_Units
C15 SUCTION TEMPAv070SERVERNo_Units
C15 LLW TEMPAv071SERVERNo_Units
C15 LSW TEMPAv072SERVERNo_Units
C16 SUCTION TEMPAv073SERVERNo_Units
C16 LLW TEMPAv074SERVERNo_Units
C16 LSW TEMPAv075SERVERNo_Units
C17 SUCTION TEMPAv076SERVERNo_Units
C17 LLW TEMPAv077SERVERNo_Units
C17 LSW TEMPAv078SERVERNo_Units
C18 SUCTION TEMPAv079SERVERNo_Units
C18 LLW TEMPAv080SERVERNo_Units
C18 LSW TEMPAv081SERVERNo_Units
C19 SUCTION TEMPAv082SERVERNo_Units
C19 LLW TEMPAv083SERVERNo_Units
C19 LSW TEMPAv084SERVERNo_Units
C20 SUCTION TEMPAv085SERVERNo_Units
C20 LLW TEMPAv086SERVERNo_Units
C20 LSW TEMPAv087SERVERNo_Units
C21 SUCTION TEMPAv088SERVERNo_Units
C21 LLW TEMPAv089SERVERNo_Units
C21 LSW TEMPAv090SERVERNo_Units
C22 SUCTION TEMPAv091SERVERNo_Units
C22 LLW TEMPAv092SERVERNo_Units
C22 LSW TEMPAv093SERVERNo_Units
C23 SUCTION TEMPAv094SERVERNo_Units
C23 LLW TEMPAv095SERVERNo_Units
C23 LSW TEMPAv096SERVERNo_Units
C24 SUCTION TEMPAv097SERVERNo_Units
C24 LLW TEMPAv098SERVERNo_Units
C24 LSW TEMPAv099SERVERNo_Units
C1 FAULTSAv100SERVERNo_Units
C2 FAULTSAv101SERVERNo_Units
C3 FAULTSAv102SERVERNo_Units
C4 FAULTSAv103SERVERNo_Units
C5 FAULTSAv104SERVERNo_Units
C6 FAULTSAv105SERVERNo_Units
C7 FAULTSAv106SERVERNo_Units
C8 FAULTSAv107SERVERNo_Units
C9 FAULTSAv108SERVERNo_Units
C10 FAULTSAv109SERVERNo_Units
C11 FAULTSAv110SERVERNo_Units
C12 FAULTSAv111SERVERNo_Units
C13 FAULTSAv112SERVERNo_Units
C14 FAULTSAv113SERVERNo_Units
C15 FAULTSAv114SERVERNo_Units
C16 FAULTSAv115SERVERNo_Units
C17 FAULTSAv116SERVERNo_Units
C18 FAULTSAv117SERVERNo_Units
C19 FAULTSAv118SERVERNo_Units
C20 FAULTSAv119SERVERNo_Units
C21 FAULTSAv120SERVERNo_Units
C22 FAULTSAv121SERVERNo_Units
C23 FAULTSAv122SERVERNo_Units
C24 FAULTSAv123SERVERNo_Units
FAULT 1 COMP #Av124SERVERNo_Units
FAULT 2 COMP #Av125SERVERNo_Units
FAULT 3 COMP #Av126SERVERNo_Units
FAULT 4 COMP #Av127SERVERNo_Units
FAULT 5 COMP #Av128SERVERNo_Units
FAULT 6 COMP #Av129SERVERNo_Units
FAULT 7 COMP #Av130SERVERNo_Units
FAULT 8 COMP #Av131SERVERNo_Units
FAULT 9 COMP #Av132SERVERNo_Units
FAULT 10 COMP #Av133SERVERNo_Units
FAULT 11 COMP #Av134SERVERNo_Units
FAULT 12 COMP #Av135SERVERNo_Units
FAULT 13 COMP #Av136SERVERNo_Units
FAULT 14 COMP #Av137SERVERNo_Units
FAULT 15 COMP #Av138SERVERNo_Units
FAULT 16 COMP #Av139SERVERNo_Units
FAULT 17 COMP #Av140SERVERNo_Units
FAULT 18 COMP #Av141SERVERNo_Units
FAULT 19 COMP #Av142SERVERNo_Units
FAULT 20 COMP #Av143SERVERNo_Units
FAULT 1 TYPEAv144SERVERNo_Units
FAULT 2 TYPEAv145SERVERNo_Units
FAULT 3 TYPEAv146SERVERNo_Units
FAULT 4 TYPEAv147SERVERNo_Units
FAULT 5 TYPEAv148SERVERNo_Units
FAULT 6 TYPEAv149SERVERNo_Units
FAULT 7 TYPEAv150SERVERNo_Units
FAULT 8 TYPEAv151SERVERNo_Units
FAULT 9 TYPEAv152SERVERNo_Units
FAULT 10 TYPEAv153SERVERNo_Units
FAULT 11 TYPEAv154SERVERNo_Units
FAULT 12 TYPEAv155SERVERNo_Units
FAULT 13 TYPEAv156SERVERNo_Units
FAULT 14 TYPEAv157SERVERNo_Units
FAULT 15 TYPEAv158SERVERNo_Units
FAULT 16 TYPEAv159SERVERNo_Units
FAULT 17 TYPEAv160SERVERNo_Units
FAULT 18 TYPEAv161SERVERNo_Units
FAULT 19 TYPEAv162SERVERNo_Units
FAULT 20 TYPEAv163SERVERNo_Units
LP0HR - HRS Cooling -00-09aV164ServerNo_Units
LP1HR - HRS Cooling -10-19aV165ServerNo_Units
LP2HR - HRS Cooling -20-29aV166ServerNo_Units
LP3HR - HRS Cooling -30-39aV167ServerNo_Units
LP4HR - HRS Cooling -40-49aV168ServerNo_Units
LP5HR - HRS Cooling -50-59aV169ServerNo_Units
LP6HR - HRS Cooling -60-69aV170ServerNo_Units
LP7HR - HRS Cooling -70-79aV171ServerNo_Units
LP8HR - HRS Cooling -80-89aV172ServerNo_Units
LP9HR - HRS Cooling -90-100aV173ServerNo_Units
HLP0HR - HRS Heating - 0-9aV174ServerNo_Units
HLP1HR - HRS Heating - 10-19aV175ServerNo_Units
HLP2HR - HRS Heating - 20-29aV176ServerNo_Units
HLP3HR - HRS Heating - 30-39aV177ServerNo_Units
HLP4HR - HRS Heating - 40-49aV178ServerNo_Units
HLP5HR - HRS Heating - 50-59aV179ServerNo_Units
HLP6HR - HRS Heating - 60-69aV180ServerNo_Units
HLP7HR - HRS Heating - 70-79aV181ServerNo_Units
HLP8HR - HRS Heating - 80-89aV182ServerNo_Units
HLP9HR - HRS Heating - 90-100aV183ServerNo_Units
COOL UPSETPTAv184SERVERNo_Units
COOL LOWSETPTAv185SERVERNo_Units
COOL VSPAv186SERVERNo_Units
COOL TDIFFAv187SERVERNo_Units
HEAT UPSETPTAv188SERVERNo_Units
HEAT LOWSETPTAv189SERVERNo_Units
HEAT VSPAv190SERVERNo_Units
HEAT TDIFFAv191SERVERNo_Units
LOAD LIMITAv192SERVERNo_Units
FAIL INDICATORAv193SERVERNo_Units
LEAD COMPRESSORAv194SERVERNo_Units
FLUSH TIMEAv195SERVERNo_Units
FLUSH DURATIONAv196SERVERNo_Units
OPERATING MODEAv197SERVERNo_Units
MOST CURRENT FLTAv198SERVERNo_Units
HEAT DELAY (READ)Av199SERVERNo_Units
HEAT DELAY (wRITE)Av200SERVERNo_Units
on_off_ctrl_readBv001Server 
ex1_faultBv002Server 
remote_on_offBv003Server 
ex3_faultBv004Server 
ex4_faultBv005Server 
low_chw_flowBv006Server 
low_cw_flowBv007Server 
LOW LLW TEMPBv008Server 
LOW LSW TEMPBv009Server 
c1_statusBv010Server 
c2_statusBv011Server 
c3_statusBv012Server 
c4_statusBv013Server 
c5_statusBv014Server 
c6_statusBv015Server 
c7_statusBv016Server 
c8_statusBv017Server 
c9_statusBv018Server 
c10_statusBv019Server 
c11_statusBv020Server 
c12_statusBv021Server 
c13_statusBv022Server 
c14_statusBv023Server 
c15_statusBv024Server 
c16_statusBv025Server 
c17_statusBv026Server 
c18_statusBv027Server 
c19_statusBv028Server 
c20_statusBv029Server 
c21_statusBv030Server 
c22_statusBv031Server 
c23_statusBv032Server 
c24_statusBv033Server 
on_off_ctrl_writeBv034Server 