Multistack Compu25 - Can you show me a sample points list for a heat pump?

The Multistack COMPU25 is a high-performance controller used in modular heat pump systems. Successful integration into a Building Automation System (BAS) requires a complete and explicit Points List to ensure every data register is mapped accurately for monitoring and control.

This technical resource provides the full, unabridged list of 200 Analog Values (Av) and 34 Binary Values (Bv). Using this explicit data helps prevent integration errors and ensures your gateway or BMS is polling the correct addresses.

Explicit Multistack COMPU25 Heat Pump Points List (Full)

The following table contains the complete set of data points available for the Multistack COMPU25. Addresses follow standard 1-based indexing for FieldServer and CAS integration tools.

Point Name Type Address Function Units
CAPACITYAv001SERVERNo_Units
DEMANDAv002SERVERNo_Units
NUMBER OF COMPSAv003SERVERNo_Units
CURRENT FAULTSAv004SERVERNo_Units
OPERATING MODEAv005SERVERNo_Units
ENT LOAD TEMPAv006SERVERNo_Units
LEV LOAD TEMPAv007SERVERNo_Units
ENT SOURCE TEMPAv008SERVERNo_Units
LEV SOURCE TEMPAv009SERVERNo_Units
COOL UPSETPTAv010SERVERNo_Units
COOL LOWSETPTAv011SERVERNo_Units
COOL VSPAv012SERVERNo_Units
COOL TDIFFAv013SERVERNo_Units
HEAT UPSETPTAv014SERVERNo_Units
HEAT LOWSETPTAv015SERVERNo_Units
HEAT VSPAv016SERVERNo_Units
HEAT TDIFFAv017SERVERNo_Units
LOAD LIMITAv018SERVERNo_Units
FAIL INDICATORAv019SERVERNo_Units
LEAD COMPRESSORAv020SERVERNo_Units
FLUSH TIMEAv021SERVERNo_Units
FLUSH DURATIONAv022SERVERNo_Units
MONTHAv023SERVERNo_Units
DAYAv024SERVERNo_Units
YEARAv025SERVERNo_Units
HOURAv026SERVERNo_Units
MINUTEAv027SERVERNo_Units
C1 SUCTION TEMPAv028SERVERNo_Units
C1 LLW TEMPAv029SERVERNo_Units
C1 LSW TEMPAv030SERVERNo_Units
C2 SUCTION TEMPAv031SERVERNo_Units
C2 LLW TEMPAv032SERVERNo_Units
C2 LSW TEMPAv033SERVERNo_Units
C3 SUCTION TEMPAv034SERVERNo_Units
C3 LLW TEMPAv035SERVERNo_Units
C3 LSW TEMPAv036SERVERNo_Units
C4 SUCTION TEMPAv037SERVERNo_Units
C4 LLW TEMPAv038SERVERNo_Units
C4 LSW TEMPAv039SERVERNo_Units
C5 SUCTION TEMPAv040SERVERNo_Units
C5 LLW TEMPAv041SERVERNo_Units
C5 LSW TEMPAv042SERVERNo_Units
C6 SUCTION TEMPAv043SERVERNo_Units
C6 LLW TEMPAv044SERVERNo_Units
C6 LSW TEMPAv045SERVERNo_Units
C7 SUCTION TEMPAv046SERVERNo_Units
C7 LLW TEMPAv047SERVERNo_Units
C7 LSW TEMPAv048SERVERNo_Units
C8 SUCTION TEMPAv049SERVERNo_Units
C8 LLW TEMPAv050SERVERNo_Units
C8 LSW TEMPAv051SERVERNo_Units
C9 SUCTION TEMPAv052SERVERNo_Units
C9 LLW TEMPAv053SERVERNo_Units
C9 LSW TEMPAv054SERVERNo_Units
C10 SUCTION TEMPAv055SERVERNo_Units
C10 LLW TEMPAv056SERVERNo_Units
C10 LSW TEMPAv057SERVERNo_Units
C11 SUCTION TEMPAv058SERVERNo_Units
C11 LLW TEMPAv059SERVERNo_Units
C11 LSW TEMPAv060SERVERNo_Units
C12 SUCTION TEMPAv061SERVERNo_Units
C12 LLW TEMPAv062SERVERNo_Units
C12 LSW TEMPAv063SERVERNo_Units
C13 SUCTION TEMPAv064SERVERNo_Units
C13 LLW TEMPAv065SERVERNo_Units
C13 LSW TEMPAv066SERVERNo_Units
C14 SUCTION TEMPAv067SERVERNo_Units
C14 LLW TEMPAv068SERVERNo_Units
C14 LSW TEMPAv069SERVERNo_Units
C15 SUCTION TEMPAv070SERVERNo_Units
C15 LLW TEMPAv071SERVERNo_Units
C15 LSW TEMPAv072SERVERNo_Units
C16 SUCTION TEMPAv073SERVERNo_Units
C16 LLW TEMPAv074SERVERNo_Units
C16 LSW TEMPAv075SERVERNo_Units
C17 SUCTION TEMPAv076SERVERNo_Units
C17 LLW TEMPAv077SERVERNo_Units
C17 LSW TEMPAv078SERVERNo_Units
C18 SUCTION TEMPAv079SERVERNo_Units
C18 LLW TEMPAv080SERVERNo_Units
C18 LSW TEMPAv081SERVERNo_Units
C19 SUCTION TEMPAv082SERVERNo_Units
C19 LLW TEMPAv083SERVERNo_Units
C19 LSW TEMPAv084SERVERNo_Units
C20 SUCTION TEMPAv085SERVERNo_Units
C20 LLW TEMPAv086SERVERNo_Units
C20 LSW TEMPAv087SERVERNo_Units
C21 SUCTION TEMPAv088SERVERNo_Units
C21 LLW TEMPAv089SERVERNo_Units
C21 LSW TEMPAv090SERVERNo_Units
C22 SUCTION TEMPAv091SERVERNo_Units
C22 LLW TEMPAv092SERVERNo_Units
C22 LSW TEMPAv093SERVERNo_Units
C23 SUCTION TEMPAv094SERVERNo_Units
C23 LLW TEMPAv095SERVERNo_Units
C23 LSW TEMPAv096SERVERNo_Units
C24 SUCTION TEMPAv097SERVERNo_Units
C24 LLW TEMPAv098SERVERNo_Units
C24 LSW TEMPAv099SERVERNo_Units
C1 FAULTSAv100SERVERNo_Units
C2 FAULTSAv101SERVERNo_Units
C3 FAULTSAv102SERVERNo_Units
C4 FAULTSAv103SERVERNo_Units
C5 FAULTSAv104SERVERNo_Units
C6 FAULTSAv105SERVERNo_Units
C7 FAULTSAv106SERVERNo_Units
C8 FAULTSAv107SERVERNo_Units
C9 FAULTSAv108SERVERNo_Units
C10 FAULTSAv109SERVERNo_Units
C11 FAULTSAv110SERVERNo_Units
C12 FAULTSAv111SERVERNo_Units
C13 FAULTSAv112SERVERNo_Units
C14 FAULTSAv113SERVERNo_Units
C15 FAULTSAv114SERVERNo_Units
C16 FAULTSAv115SERVERNo_Units
C17 FAULTSAv116SERVERNo_Units
C18 FAULTSAv117SERVERNo_Units
C19 FAULTSAv118SERVERNo_Units
C20 FAULTSAv119SERVERNo_Units
C21 FAULTSAv120SERVERNo_Units
C22 FAULTSAv121SERVERNo_Units
C23 FAULTSAv122SERVERNo_Units
C24 FAULTSAv123SERVERNo_Units
FAULT 1 COMP #Av124SERVERNo_Units
FAULT 2 COMP #Av125SERVERNo_Units
FAULT 3 COMP #Av126SERVERNo_Units
FAULT 4 COMP #Av127SERVERNo_Units
FAULT 5 COMP #Av128SERVERNo_Units
FAULT 6 COMP #Av129SERVERNo_Units
FAULT 7 COMP #Av130SERVERNo_Units
FAULT 8 COMP #Av131SERVERNo_Units
FAULT 9 COMP #Av132SERVERNo_Units
FAULT 10 COMP #Av133SERVERNo_Units
FAULT 11 COMP #Av134SERVERNo_Units
FAULT 12 COMP #Av135SERVERNo_Units
FAULT 13 COMP #Av136SERVERNo_Units
FAULT 14 COMP #Av137SERVERNo_Units
FAULT 15 COMP #Av138SERVERNo_Units
FAULT 16 COMP #Av139SERVERNo_Units
FAULT 17 COMP #Av140SERVERNo_Units
FAULT 18 COMP #Av141SERVERNo_Units
FAULT 19 COMP #Av142SERVERNo_Units
FAULT 20 COMP #Av143SERVERNo_Units
FAULT 1 TYPEAv144SERVERNo_Units
FAULT 2 TYPEAv145SERVERNo_Units
FAULT 3 TYPEAv146SERVERNo_Units
FAULT 4 TYPEAv147SERVERNo_Units
FAULT 5 TYPEAv148SERVERNo_Units
FAULT 6 TYPEAv149SERVERNo_Units
FAULT 7 TYPEAv150SERVERNo_Units
FAULT 8 TYPEAv151SERVERNo_Units
FAULT 9 TYPEAv152SERVERNo_Units
FAULT 10 TYPEAv153SERVERNo_Units
FAULT 11 TYPEAv154SERVERNo_Units
FAULT 12 TYPEAv155SERVERNo_Units
FAULT 13 TYPEAv156SERVERNo_Units
FAULT 14 TYPEAv157SERVERNo_Units
FAULT 15 TYPEAv158SERVERNo_Units
FAULT 16 TYPEAv159SERVERNo_Units
FAULT 17 TYPEAv160SERVERNo_Units
FAULT 18 TYPEAv161SERVERNo_Units
FAULT 19 TYPEAv162SERVERNo_Units
FAULT 20 TYPEAv163SERVERNo_Units
LP0HR - HRS Cooling 00-09aV164ServerNo_Units
LP1HR - HRS Cooling 10-19aV165ServerNo_Units
LP2HR - HRS Cooling 20-29aV166ServerNo_Units
LP3HR - HRS Cooling 30-39aV167ServerNo_Units
LP4HR - HRS Cooling 40-49aV168ServerNo_Units
LP5HR - HRS Cooling 50-59aV169ServerNo_Units
LP6HR - HRS Cooling 60-69aV170ServerNo_Units
LP7HR - HRS Cooling 70-79aV171ServerNo_Units
LP8HR - HRS Cooling 80-89aV172ServerNo_Units
LP9HR - HRS Cooling 90-100aV173ServerNo_Units
HLP0HR - HRS Heating 0-9aV174ServerNo_Units
HLP1HR - HRS Heating 10-19aV175ServerNo_Units
HLP2HR - HRS Heating 20-29aV176ServerNo_Units
HLP3HR - HRS Heating 30-39aV177ServerNo_Units
HLP4HR - HRS Heating 40-49aV178ServerNo_Units
HLP5HR - HRS Heating 50-59aV179ServerNo_Units
HLP6HR - HRS Heating 60-69aV180ServerNo_Units
HLP7HR - HRS Heating 70-79aV181ServerNo_Units
HLP8HR - HRS Heating 80-89aV182ServerNo_Units
HLP9HR - HRS Heating 90-100aV183ServerNo_Units
COOL UPSETPTAv184SERVERNo_Units
COOL LOWSETPTAv185SERVERNo_Units
COOL VSPAv186SERVERNo_Units
COOL TDIFFAv187SERVERNo_Units
HEAT UPSETPTAv188SERVERNo_Units
HEAT LOWSETPTAv189SERVERNo_Units
HEAT VSPAv190SERVERNo_Units
HEAT TDIFFAv191SERVERNo_Units
LOAD LIMITAv192SERVERNo_Units
FAIL INDICATORAv193SERVERNo_Units
LEAD COMPRESSORAv194SERVERNo_Units
FLUSH TIMEAv195SERVERNo_Units
FLUSH DURATIONAv196SERVERNo_Units
OPERATING MODEAv197SERVERNo_Units
MOST CURRENT FLTAv198SERVERNo_Units
HEAT DELAY (READ)Av199SERVERNo_Units
HEAT DELAY (WRITE)Av200SERVERNo_Units
on_off_ctrl_readBv001ServerN/A
ex1_faultBv002ServerN/A
remote_on_offBv003ServerN/A
ex3_faultBv004ServerN/A
ex4_faultBv005ServerN/A
low_chw_flowBv006ServerN/A
low_cw_flowBv007ServerN/A
LOW LLW TEMPBv008ServerN/A
LOW LSW TEMPBv009ServerN/A
c1_statusBv010ServerN/A
c2_statusBv011ServerN/A
c3_statusBv012ServerN/A
c4_statusBv013ServerN/A
c5_statusBv014ServerN/A
c6_statusBv015ServerN/A
c7_statusBv016ServerN/A
c8_statusBv017ServerN/A
c9_statusBv018ServerN/A
c10_statusBv019ServerN/A
c11_statusBv020ServerN/A
c12_statusBv021ServerN/A
c13_statusBv022ServerN/A
c14_statusBv023ServerN/A
c15_statusBv024ServerN/A
c16_statusBv025ServerN/A
c17_statusBv026ServerN/A
c18_statusBv027ServerN/A
c19_statusBv028ServerN/A
c20_statusBv029ServerN/A
c21_statusBv030ServerN/A
c22_statusBv031ServerN/A
c23_statusBv032ServerN/A
c24_statusBv033ServerN/A
on_off_ctrl_writeBv034ServerN/A

Integration Best Practices

  • Always verify the specific firmware version of your Multistack controller, as point mapping can shift between releases.
  • Ensure your gateway is configured to distinguish between Analog Values (Av) and Binary Values (Bv), even if they share the same numeric address.
  • Monitor the Current Faults register to trigger alerts in your BMS for proactive system maintenance.
  • Use CAS Modbus Scanner or CAS BACnet Explorer to verify point data before finalizing your integration.