Multistack Support, Knowledge and FAQ

Data Sheets and Manuals

PDF gif Image  –  Data Sheet – FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller

PDF gif Image  –  Manual – FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller

PDF gif Image  –  FieldServer Driver – Serial – FS-8705-18 – Multistack Comput25 Master Controller

PDF gif Image  –  FieldServer Driver Manual – Serial – FS-8705-18 – Multistack Comput25 Master Controller

PDF gif Image  –  Multistack – The Modular Water Chiller – Master Control User Manual

PDF gif Image  –  BACnet Portal Technical Manual Multistack – The Modular Water Chiller – (MS20/30/50 Application – BACnet over TCP/IP )

PDF gif Image  –  Multistack – The Modular Water Chiller – BACnet Portal Technical Manual (MS20/30/50 Application – BACnet over TCP/IP Heat Pump)More Data Sheets

Points List

This points list may change when firmware is updated or the device is configured differently. Contact us to check for the lastest points list.

Water Cooler Chiller

Map_Descriptor_NameData_TypeAddressFunctionUnits
num_of_compressorsAv001ServerNo_Units
capacityAv002ServerNo_Units
demandAv003ServerNo_Units
current_faultsAv004ServerNo_Units
echw_sys_tempAv005ServerNo_Units
lchw_sys_tempAv006ServerNo_Units
ecw_sys_tempAv007ServerNo_Units
lcw_sys_tempAv008ServerNo_Units
lead_comp_readAv009ServerNo_Units
load_limit_readAv010ServerNo_Units
upsetpt_readAv011ServerNo_Units
lowsetpt_readAv012ServerNo_Units
vsp_readAv013ServerNo_Units
tdiff_readAv014ServerNo_Units
fail_indic_readAv015ServerNo_Units
flush_time_readAv016ServerNo_Units
flush_duration_readAv017ServerNo_Units
monthAv018ServerNo_Units
dayAv019ServerNo_Units
yearAv020ServerNo_Units
hourAv021ServerNo_Units
minuteAv022ServerNo_Units
faults_c1Av023ServerNo_Units
faults_c2Av024ServerNo_Units
faults_c3Av025ServerNo_Units
faults_c4Av026ServerNo_Units
faults_c5Av027ServerNo_Units
faults_c6Av028ServerNo_Units
faults_c7Av029ServerNo_Units
faults_c8Av030ServerNo_Units
faults_c9Av031ServerNo_Units
faults_c10Av032ServerNo_Units
faults_c11Av033ServerNo_Units
faults_c12Av034ServerNo_Units
faults_c13Av035ServerNo_Units
faults_c14Av036ServerNo_Units
faults_c15Av037ServerNo_Units
faults_c16Av038ServerNo_Units
faults_c17Av039ServerNo_Units
faults_c18Av040ServerNo_Units
faults_c19Av041ServerNo_Units
faults_c20Av042ServerNo_Units
faults_c21Av043ServerNo_Units
faults_c22Av044ServerNo_Units
faults_c23Av045ServerNo_Units
faults_c24Av046ServerNo_Units
c1_suct_tempAv047ServerNo_Units
c1_lchw_tempAv048ServerNo_Units
c2_suct_tempAv049ServerNo_Units
c2_lchw_tempAv050ServerNo_Units
c3_suct_tempAv051ServerNo_Units
c3_lchw_tempAv052ServerNo_Units
c4_suct_tempAv053ServerNo_Units
c4_lchw_tempAv054ServerNo_Units
c5_suct_tempAv055ServerNo_Units
c5_lchw_tempAv056ServerNo_Units
c6_suct_tempAv057ServerNo_Units
c6_lchw_tempAv058ServerNo_Units
c7_suct_tempAv059ServerNo_Units
c7_lchw_tempAv060ServerNo_Units
c8_suct_tempAv061ServerNo_Units
c8_lchw_tempAv062ServerNo_Units
c9_suct_tempAv063ServerNo_Units
c9_lchw_tempAv064ServerNo_Units
c10_suct_tempAv065ServerNo_Units
c10_lchw_tempAv066ServerNo_Units
c11_suct_tempAv067ServerNo_Units
c11_lchw_tempAv068ServerNo_Units
c12_suct_tempAv069ServerNo_Units
c12_lchw_tempAv070ServerNo_Units
c13_suct_tempAv071ServerNo_Units
c13_lchw_tempAv072ServerNo_Units
c14_suct_tempAv073ServerNo_Units
c14_lchw_tempAv074ServerNo_Units
c15_suct_tempAv075ServerNo_Units
c15_lchw_tempAv076ServerNo_Units
c16_suct_tempAv077ServerNo_Units
c16_lchw_tempAv078ServerNo_Units
c17_suct_tempAv079ServerNo_Units
c17_lchw_tempAv080ServerNo_Units
c18_suct_tempAv081ServerNo_Units
c18_lchw_tempAv082ServerNo_Units
c19_suct_tempAv083ServerNo_Units
c19_lchw_tempAv084ServerNo_Units
c20_suct_tempAv085ServerNo_Units
c20_lchw_tempAv086ServerNo_Units
c21_suct_tempAv087ServerNo_Units
c21_lchw_tempAv088ServerNo_Units
c22_suct_tempAv089ServerNo_Units
c22_lchw_tempAv090ServerNo_Units
c23_suct_tempAv091ServerNo_Units
c23_lchw_tempAv092ServerNo_Units
c24_suct_tempAv093ServerNo_Units
c24_lchw_tempAv094ServerNo_Units
fault_1_typeAv095ServerNo_Units
fault_2_typeAv096ServerNo_Units
fault_3_typeAv097ServerNo_Units
fault_4_typeAv098ServerNo_Units
fault_5_typeAv099ServerNo_Units
fault_6_typeAv100ServerNo_Units
fault_7_typeAv101ServerNo_Units
fault_8_typeAv102ServerNo_Units
fault_9_typeAv103ServerNo_Units
fault_10_typeAv104ServerNo_Units
fault_11_typeAv105ServerNo_Units
fault_12_typeAv106ServerNo_Units
fault_13_typeAv107ServerNo_Units
fault_14_typeAv108ServerNo_Units
fault_15_typeAv109ServerNo_Units
fault_16_typeAv110ServerNo_Units
fault_17_typeAv111ServerNo_Units
fault_18_typeAv112ServerNo_Units
fault_19_typeAv113ServerNo_Units
fault_20_typeAv114ServerNo_Units
fault_1_compAv115ServerNo_Units
fault_2_compAv116ServerNo_Units
fault_3_compAv117ServerNo_Units
fault_4_compAv118ServerNo_Units
fault_5_compAv119ServerNo_Units
fault_6_compAv120ServerNo_Units
fault_7_compAv121ServerNo_Units
fault_8_compAv122ServerNo_Units
fault_9_compAv123ServerNo_Units
fault_10_compAv124ServerNo_Units
fault_11_compAv125ServerNo_Units
fault_12_compAv126ServerNo_Units
fault_13_compAv127ServerNo_Units
fault_14_compAv128ServerNo_Units
fault_15_compAv129ServerNo_Units
fault_16_compAv130ServerNo_Units
fault_17_compAv131ServerNo_Units
fault_18_compAv132ServerNo_Units
fault_19_compAv133ServerNo_Units
fault_20_compAv134ServerNo_Units
upsetpt_writeAv135ServerNo_Units
lowsetpt_writeAv136ServerNo_Units
vsp_writeAv137ServerNo_Units
load_limit_writeAv138ServerNo_Units
tdiff_writeAv139ServerNo_Units
fail_indic_writeAv140ServerNo_Units
lead_comp_writeAv141ServerNo_Units
flush_time_writeAv142ServerNo_Units
flush_duration_writeAv143ServerNo_Units
LP0HR – HRS 144rating 00-144Av144ServerNo_Units
LP1HR – HRS 145rating 10-145Av145ServerNo_Units
LP2HR – HRS 146rating 20-146Av146ServerNo_Units
LP3HR – HRS 147rating 30-147Av147ServerNo_Units
LP4HR – HRS 148rating 40-148Av148ServerNo_Units
LP5HR – HRS 149rating 50-149Av149ServerNo_Units
LP6HR – HRS 150rating 60-150Av150ServerNo_Units
LP7HR – HRS 151rating 70-151Av151ServerNo_Units
LP8HR – HRS 152rating 80-152Av152ServerNo_Units
LP9HR – HRS 153rating 90-153Av153ServerNo_Units
most_crnt_fltAv154ServerNo_Units
on_off_ctrl_readBv001Server
ex1_faultBv002Server
remote_on_offBv003Server
ex3_faultBv004Server
ex4_faultBv005Server
low_chw_flowBv006Server
low_cw_flowBv007Server
low_chw_tempBv008Server
c1_statusBv009Server
c2_statusBv010Server
c3_statusBv011Server
c4_statusBv012Server
c5_statusBv013Server
c6_statusBv014Server
c7_statusBv015Server
c8_statusBv016Server
c9_statusBv017Server
c10_statusBv018Server
c11_statusBv019Server
c12_statusBv020Server
c13_statusBv021Server
c14_statusBv022Server
c15_statusBv023Server
c16_statusBv024Server
c17_statusBv025Server
c18_statusBv026Server
c19_statusBv027Server
c20_statusBv028Server
c21_statusBv029Server
c22_statusBv030Server
c23_statusBv031Server
c24_statusBv032Server
on_off_ctrl_writeBv033Server

Heat Pumps

Map_Descriptor_NameData_TypeAddressFunctionUnits
CAPACITYAv001SERVERNo_Units
DEMANDAv002SERVERNo_Units
NUMBER OF COMPSAv003SERVERNo_Units
CURRENT FAULTSAv004SERVERNo_Units
OPERATING MODEAv005SERVERNo_Units
ENT LOAD TEMPAv006SERVERNo_Units
LEV LOAD TEMPAv007SERVERNo_Units
ENT SOURCE TEMPAv008SERVERNo_Units
LEV SOURCE TEMPAv009SERVERNo_Units
COOL UPSETPTAv010SERVERNo_Units
COOL LOWSETPTAv011SERVERNo_Units
COOL VSPAv012SERVERNo_Units
COOL TDIFFAv013SERVERNo_Units
HEAT UPSETPTAv014SERVERNo_Units
HEAT LOWSETPTAv015SERVERNo_Units
HEAT VSPAv016SERVERNo_Units
HEAT TDIFFAv017SERVERNo_Units
LOAD LIMITAv018SERVERNo_Units
FAIL INDICATORAv019SERVERNo_Units
LEAD COMPRESSORAv020SERVERNo_Units
FLUSH TIMEAv021SERVERNo_Units
FLUSH DURATIONAv022SERVERNo_Units
MONTHAv023SERVERNo_Units
DAYAv024SERVERNo_Units
YEARAv025SERVERNo_Units
HOURAv026SERVERNo_Units
MINUTEAv027SERVERNo_Units
C1 SUCTION TEMPAv028SERVERNo_Units
C1 LLW TEMPAv029SERVERNo_Units
C1 LSW TEMPAv030SERVERNo_Units
C2 SUCTION TEMPAv031SERVERNo_Units
C2 LLW TEMPAv032SERVERNo_Units
C2 LSW TEMPAv033SERVERNo_Units
C3 SUCTION TEMPAv034SERVERNo_Units
C3 LLW TEMPAv035SERVERNo_Units
C3 LSW TEMPAv036SERVERNo_Units
C4 SUCTION TEMPAv037SERVERNo_Units
C4 LLW TEMPAv038SERVERNo_Units
C4 LSW TEMPAv039SERVERNo_Units
C5 SUCTION TEMPAv040SERVERNo_Units
C5 LLW TEMPAv041SERVERNo_Units
C5 LSW TEMPAv042SERVERNo_Units
C6 SUCTION TEMPAv043SERVERNo_Units
C6 LLW TEMPAv044SERVERNo_Units
C6 LSW TEMPAv045SERVERNo_Units
C7 SUCTION TEMPAv046SERVERNo_Units
C7 LLW TEMPAv047SERVERNo_Units
C7 LSW TEMPAv048SERVERNo_Units
C8 SUCTION TEMPAv049SERVERNo_Units
C8 LLW TEMPAv050SERVERNo_Units
C8 LSW TEMPAv051SERVERNo_Units
C9 SUCTION TEMPAv052SERVERNo_Units
C9 LLW TEMPAv053SERVERNo_Units
C9 LSW TEMPAv054SERVERNo_Units
C10 SUCTION TEMPAv055SERVERNo_Units
C10 LLW TEMPAv056SERVERNo_Units
C10 LSW TEMPAv057SERVERNo_Units
C11 SUCTION TEMPAv058SERVERNo_Units
C11 LLW TEMPAv059SERVERNo_Units
C11 LSW TEMPAv060SERVERNo_Units
C12 SUCTION TEMPAv061SERVERNo_Units
C12 LLW TEMPAv062SERVERNo_Units
C12 LSW TEMPAv063SERVERNo_Units
C13 SUCTION TEMPAv064SERVERNo_Units
C13 LLW TEMPAv065SERVERNo_Units
C13 LSW TEMPAv066SERVERNo_Units
C14 SUCTION TEMPAv067SERVERNo_Units
C14 LLW TEMPAv068SERVERNo_Units
C14 LSW TEMPAv069SERVERNo_Units
C15 SUCTION TEMPAv070SERVERNo_Units
C15 LLW TEMPAv071SERVERNo_Units
C15 LSW TEMPAv072SERVERNo_Units
C16 SUCTION TEMPAv073SERVERNo_Units
C16 LLW TEMPAv074SERVERNo_Units
C16 LSW TEMPAv075SERVERNo_Units
C17 SUCTION TEMPAv076SERVERNo_Units
C17 LLW TEMPAv077SERVERNo_Units
C17 LSW TEMPAv078SERVERNo_Units
C18 SUCTION TEMPAv079SERVERNo_Units
C18 LLW TEMPAv080SERVERNo_Units
C18 LSW TEMPAv081SERVERNo_Units
C19 SUCTION TEMPAv082SERVERNo_Units
C19 LLW TEMPAv083SERVERNo_Units
C19 LSW TEMPAv084SERVERNo_Units
C20 SUCTION TEMPAv085SERVERNo_Units
C20 LLW TEMPAv086SERVERNo_Units
C20 LSW TEMPAv087SERVERNo_Units
C21 SUCTION TEMPAv088SERVERNo_Units
C21 LLW TEMPAv089SERVERNo_Units
C21 LSW TEMPAv090SERVERNo_Units
C22 SUCTION TEMPAv091SERVERNo_Units
C22 LLW TEMPAv092SERVERNo_Units
C22 LSW TEMPAv093SERVERNo_Units
C23 SUCTION TEMPAv094SERVERNo_Units
C23 LLW TEMPAv095SERVERNo_Units
C23 LSW TEMPAv096SERVERNo_Units
C24 SUCTION TEMPAv097SERVERNo_Units
C24 LLW TEMPAv098SERVERNo_Units
C24 LSW TEMPAv099SERVERNo_Units
C1 FAULTSAv100SERVERNo_Units
C2 FAULTSAv101SERVERNo_Units
C3 FAULTSAv102SERVERNo_Units
C4 FAULTSAv103SERVERNo_Units
C5 FAULTSAv104SERVERNo_Units
C6 FAULTSAv105SERVERNo_Units
C7 FAULTSAv106SERVERNo_Units
C8 FAULTSAv107SERVERNo_Units
C9 FAULTSAv108SERVERNo_Units
C10 FAULTSAv109SERVERNo_Units
C11 FAULTSAv110SERVERNo_Units
C12 FAULTSAv111SERVERNo_Units
C13 FAULTSAv112SERVERNo_Units
C14 FAULTSAv113SERVERNo_Units
C15 FAULTSAv114SERVERNo_Units
C16 FAULTSAv115SERVERNo_Units
C17 FAULTSAv116SERVERNo_Units
C18 FAULTSAv117SERVERNo_Units
C19 FAULTSAv118SERVERNo_Units
C20 FAULTSAv119SERVERNo_Units
C21 FAULTSAv120SERVERNo_Units
C22 FAULTSAv121SERVERNo_Units
C23 FAULTSAv122SERVERNo_Units
C24 FAULTSAv123SERVERNo_Units
FAULT 1 COMP #Av124SERVERNo_Units
FAULT 2 COMP #Av125SERVERNo_Units
FAULT 3 COMP #Av126SERVERNo_Units
FAULT 4 COMP #Av127SERVERNo_Units
FAULT 5 COMP #Av128SERVERNo_Units
FAULT 6 COMP #Av129SERVERNo_Units
FAULT 7 COMP #Av130SERVERNo_Units
FAULT 8 COMP #Av131SERVERNo_Units
FAULT 9 COMP #Av132SERVERNo_Units
FAULT 10 COMP #Av133SERVERNo_Units
FAULT 11 COMP #Av134SERVERNo_Units
FAULT 12 COMP #Av135SERVERNo_Units
FAULT 13 COMP #Av136SERVERNo_Units
FAULT 14 COMP #Av137SERVERNo_Units
FAULT 15 COMP #Av138SERVERNo_Units
FAULT 16 COMP #Av139SERVERNo_Units
FAULT 17 COMP #Av140SERVERNo_Units
FAULT 18 COMP #Av141SERVERNo_Units
FAULT 19 COMP #Av142SERVERNo_Units
FAULT 20 COMP #Av143SERVERNo_Units
FAULT 1 TYPEAv144SERVERNo_Units
FAULT 2 TYPEAv145SERVERNo_Units
FAULT 3 TYPEAv146SERVERNo_Units
FAULT 4 TYPEAv147SERVERNo_Units
FAULT 5 TYPEAv148SERVERNo_Units
FAULT 6 TYPEAv149SERVERNo_Units
FAULT 7 TYPEAv150SERVERNo_Units
FAULT 8 TYPEAv151SERVERNo_Units
FAULT 9 TYPEAv152SERVERNo_Units
FAULT 10 TYPEAv153SERVERNo_Units
FAULT 11 TYPEAv154SERVERNo_Units
FAULT 12 TYPEAv155SERVERNo_Units
FAULT 13 TYPEAv156SERVERNo_Units
FAULT 14 TYPEAv157SERVERNo_Units
FAULT 15 TYPEAv158SERVERNo_Units
FAULT 16 TYPEAv159SERVERNo_Units
FAULT 17 TYPEAv160SERVERNo_Units
FAULT 18 TYPEAv161SERVERNo_Units
FAULT 19 TYPEAv162SERVERNo_Units
FAULT 20 TYPEAv163SERVERNo_Units
LP0HR – HRS Cooling -00-09aV164ServerNo_Units
LP1HR – HRS Cooling -10-19aV165ServerNo_Units
LP2HR – HRS Cooling -20-29aV166ServerNo_Units
LP3HR – HRS Cooling -30-39aV167ServerNo_Units
LP4HR – HRS Cooling -40-49aV168ServerNo_Units
LP5HR – HRS Cooling -50-59aV169ServerNo_Units
LP6HR – HRS Cooling -60-69aV170ServerNo_Units
LP7HR – HRS Cooling -70-79aV171ServerNo_Units
LP8HR – HRS Cooling -80-89aV172ServerNo_Units
LP9HR – HRS Cooling -90-100aV173ServerNo_Units
HLP0HR – HRS Heating – 0-9aV174ServerNo_Units
HLP1HR – HRS Heating – 10-19aV175ServerNo_Units
HLP2HR – HRS Heating – 20-29aV176ServerNo_Units
HLP3HR – HRS Heating – 30-39aV177ServerNo_Units
HLP4HR – HRS Heating – 40-49aV178ServerNo_Units
HLP5HR – HRS Heating – 50-59aV179ServerNo_Units
HLP6HR – HRS Heating – 60-69aV180ServerNo_Units
HLP7HR – HRS Heating – 70-79aV181ServerNo_Units
HLP8HR – HRS Heating – 80-89aV182ServerNo_Units
HLP9HR – HRS Heating – 90-100aV183ServerNo_Units
COOL UPSETPTAv184SERVERNo_Units
COOL LOWSETPTAv185SERVERNo_Units
COOL VSPAv186SERVERNo_Units
COOL TDIFFAv187SERVERNo_Units
HEAT UPSETPTAv188SERVERNo_Units
HEAT LOWSETPTAv189SERVERNo_Units
HEAT VSPAv190SERVERNo_Units
HEAT TDIFFAv191SERVERNo_Units
LOAD LIMITAv192SERVERNo_Units
FAIL INDICATORAv193SERVERNo_Units
LEAD COMPRESSORAv194SERVERNo_Units
FLUSH TIMEAv195SERVERNo_Units
FLUSH DURATIONAv196SERVERNo_Units
OPERATING MODEAv197SERVERNo_Units
MOST CURRENT FLTAv198SERVERNo_Units
HEAT DELAY (READ)Av199SERVERNo_Units
HEAT DELAY (wRITE)Av200SERVERNo_Units
on_off_ctrl_readBv001Server
ex1_faultBv002Server
remote_on_offBv003Server
ex3_faultBv004Server
ex4_faultBv005Server
low_chw_flowBv006Server
low_cw_flowBv007Server
LOW LLW TEMPBv008Server
LOW LSW TEMPBv009Server
c1_statusBv010Server
c2_statusBv011Server
c3_statusBv012Server
c4_statusBv013Server
c5_statusBv014Server
c6_statusBv015Server
c7_statusBv016Server
c8_statusBv017Server
c9_statusBv018Server
c10_statusBv019Server
c11_statusBv020Server
c12_statusBv021Server
c13_statusBv022Server
c14_statusBv023Server
c15_statusBv024Server
c16_statusBv025Server
c17_statusBv026Server
c18_statusBv027Server
c19_statusBv028Server
c20_statusBv029Server
c21_statusBv030Server
c22_statusBv031Server
c23_statusBv032Server
c24_statusBv033Server
on_off_ctrl_writeBv034Server

Photos

mutistack4.jpg

multistack2.jpg

multistack3.jpg