Question: Broadcast traffic is being blocked on my network, Can I still use CAS BACnet Explorer?
Answer:
Yes, but with some restrictions.
The BACnet discovery uses two services – called 'Who-Is'…
Q: Can I use a T connection to connect a BACnet MSTP device?
A: No you can not use a T connection, MSTP requires both
the positive and negative wires.Note: MS/TP actually requires 3 wires.…
This step-by-step article explains how to activate CAS BACnet Key.
First of all, a user should make sure that he or she has downloaded CAS
BACnet Explorer&nb…
BACnet Integration Solutions
Chipkin has BACnet solutions for almost every situation. We have over 20+ years experience in BACnet
integration, check out our BACnet Products:…
The CAS BACnet Explorer can disable the Read Property Multiple Request as per the directions mentioned below :
Directions:Open CAS BACnet ExplorerOpen the settings dialogFrom the menu on the left ha…
Normally a binary output will uses a BACnetBinaryPV(ENUMERATED) data type for the present value. The enumeration has one of two values 0=inactive, and 1=active.BACnetBinaryPV ::= ENUMERATED {inacti…
Most BACnet devices set the device object identifier via some custom configuration software or physical switch on the device. A small and growing amount of devices allow you to configure the devi…
The Present_Value property of a Multistate Object may not have the value zero. This is specified in the BACnet specification. For example in paragraph 12.20.4 Present_Value of the 2008 Spec."The Pre…